A1-User’s Manual
56
7.8
Run Command Source to Modbus RS-485
Diagram
Programming A1 Parameters
Set Frequency Setpoint
Diagram
Programming A1 Parameters
On Keypad, program following parameters with corresponding values:
Code
Set Value
Description
22.03
3
Frequency Command by Modbus RS-485
50.01
1
Communication node (1 ~ 32)
50.02
0
Modbus baud rate (2,400bps ~ 19,200bps)
Set Frequency Setpoint
Data: (FWD: 0x0001, REV: 0x0002, RST: 0x0004)
Ref to ‘8.2.23 RS-485(Modbus)’.
Terminal
connector
Signal Descriptions
RXP
RS - 485+
RXN
RS - 485-
RXP
RXN
MODBUS RS-485
Max 19.2kbps
120O
Terminating resistance
selection switch(SW1)
VFD