A1-User’s Manual
6
2.1.3
400V class (260A ~ 296A)
Model A1-xxxA
(Note1)
-4
260
296
-
-
-
-
Motor Applied [kW]
(Note2)
HD
110
132
-
-
-
-
ND
132
160
-
-
-
-
Rated
Output
Rated Output
(Note3)
Current [A]
HD
217
260
-
-
-
-
ND
260
296
-
-
-
-
Rated
Capacity [kVA]
HD
380V
143
171
-
-
-
-
480V
180
216
-
-
-
-
ND
380V
171
195
-
-
-
-
480V
216
246
-
-
-
-
Output Frequency [Hz]
0~400Hz
(Note4)
Output Voltage [V]
3 Phase 380~480V
(Note5)
Rated
Input
Available Voltage [V]
3-phase 380~480V (± 10%)
Input Frequency [Hz]
50/ 60Hz (± 5%)
Rated Input Current [A]
HD
218.5
262.2
-
-
-
-
ND
262.2
317.8
-
-
-
-
Power loss [kW]
HD
2.20
2.64
-
-
-
-
ND
2.64
3.20
-
-
-
-
EMC Filter
Built-in 61800-3 C3
Note 1) The number that has included at model name means rated current of VFD
Note 2) Motor Applied indicates the maximum capacity applied to use of a standard 4 pole standard motor.
Note 3) The output of rated current is limited according to setting of the carrier frequency.
Note 4) In case of Sensorless, you can set the frequency at up to 300Hz by selecting 2
as the
'98.01' (Motor control mode)
Note 5) The maximum output voltage does not go up over the supplied power voltage. You can select the
output voltage as you want below the supplied power voltage.
Содержание iMASTER - A1 Series
Страница 1: ...A1 User s Manual iMASTER A1 User s Manual Doc No ADT A1 01 E201709 04...
Страница 32: ...A1 User s Manual Power terminal F1 F2 Power terminal F3 F6...
Страница 41: ...A1 User s Manual 4 Dimensions Panel Mount Unit mm inch 50 1 97 10 0 39 30 1 18 31 1 22 13 0 51 90 3 54 2 3 5...