3000EN Series: Installation Instructions
4-2
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*27
Powerline Carrier Device (X-10)
House ID
0 = A
6 = G
# + 11 = L
1 = B
7 = H
# + 12 = M
2 = C
8 = I
# + 13 = N
3 = D
9 = J
# + 14 = O
4 = E
# + 10 = K
# + 15 = P
5 = F
Powerline Carrier devices require a House ID, identified in
this field. Program Powerline Carrier devices in interactive
modes
∗
79, *80 and *81.
Not intended for fire or UL installations.
*28
Access Code for Phone Module
1-9 = first digit of access code
∗
or # = second digit of access code
(enter # +11 for “
∗
”, or # +12 for “#”)
You need to assign a 2-digit access code for the 4286 Phone
Module, if used. Example: If desired access code is 7
∗
, 7 is the
first entry, and [#] + 11 (for
∗
) is the second entry.
NOTE:
A “0” in either digit disables the phone module.
Must be “00” for UL Commercial Burglar Alarm installations.
*29
Enable IP/GSM – Communication
Device Menu Mode
(pass-through programming)
Use this Menu mode to program IP/GSM communication
device options. See
∗
29 Menu Mode section later in this
document.
Program the radio for device address 3.
Zone Sounds & Timing (
∗∗∗∗
31–
∗∗∗∗
39)
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*31
Single Alarm Sounding Per Zone
(per armed period)
0 = no limit on alarm sounding per
zone
1 = limit alarm sounding to once per
arming period for a given zone
Select whether alarm sounding (on the bell output) should be
limited to once per arming period or be unlimited.
SIA NOTE:
If “0” selected, “alarm sounding per zone” will be
the same as the “number of reports in armed period” set in
field *93 (1 if one report, 2 if 2 reports, unlimited for zones in
zone list 7).
*32
Fire Alarm Sounder Timeout
0 = yes; fire sounder timeout after time
programmed in field
∗
33
1 = no fire sounder timeout; continue
sounding until manually turned off
This control complies with NFPA requirements for temporal
pulse sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the
following:
3 pulses – pause – 3 pulses – pause – 3 pulses.
UL fire alarm installations: must be 1.
*33
Alarm Sounder Timeout
0 = No timeout
3 = 12 min
1 = 4 min
4 = 16 min
2 = 8 min
This field determines whether the external sounder will shut
off after time allotted, or continue until manually turned off.
UL installations: For residential fire alarm installation, must
be set for a minimum of 4 min (option 1); for UL Commercial
Burglary installations, must be minimum of 16 min (option 4).
*34
Exit Delay
45 - 96 = 45 - 96 seconds
97 = 120 seconds
NOTE
: Entries less than 45 will result in a
45-second delay.
The system waits the time entered before arming entry/exit
zones. If the entry/exit door is left open after this time
expires, an alarm will occur. Common zones use same delay
as partition 1.
UL installations: For UL Commercial Burglar Alarm and UL
Residential Burglar Alarm installations with line security,
total exit time must not exceed 60 seconds.
SIA Installations: minimum exit delay is 45 seconds
*35
Entry Delay 1
30 - 96 = 30 - 96 seconds
97 = 120 seconds
98 = 180 seconds
99 = 240 seconds
NOTE
: Entries less than 30 will result in a
30-second delay.
Upon entering, the system must be disarmed before the time
entered expires, otherwise it sounds an alarm. Common zones
use same delay as partition 1.
UL installations: For UL Residential Burglary Alarm
installations, must be set for a maximum of 30 seconds; entry
delay plus dial delay should not exceed 1 min. For UL
Commercial Burglar Alarm, total entry delay may not exceed
45 seconds.
SIA Installations: minimum entry delay is 30 seconds
Содержание Enterpreneur 3000EN
Страница 64: ...3000EN Series Installation Instructions 6 6...
Страница 68: ...3000EN Series Installation Instructions 8 2...
Страница 78: ...3000EN Series Installation Instructions 12 2...
Страница 82: ...13 4...
Страница 88: ...3000EN Series Installation Instructions 14 6...
Страница 92: ...3000EN SERIES INSTALLATION INSTRUCTIONS 15 4...
Страница 96: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 2 NOTES...
Страница 97: ...17 3 NOTES...
Страница 98: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 4 NOTES...
Страница 104: ...ADT Security Services Inc One Town Center Rd Boca Raton FL 33486 Copyright 2003 K5305V8s K5305V8 11 10 Rev A SIA...