ADOS S.R.L. Buccinasco (MI)
417-MTA200I1
Rev. 9
Page 41 of 77
List of Coils supported by A200E
Coil
Number
Function
0
Power On Flag reset request
1
ZERO request
2
START/ACK (charge) request
3
START/ACK (discharge) request
4
PAUSE/ABORT request
5
Totalizers reset request
6
Totalizer component 1 reset request
7
Totalizer component 2 reset request
8
Totalizer component 3 reset request
9
Totalizer unload component reset request
10
GROSS request
11
NET request
12
TARE request
13
TOTAL value reset request
14
PEAK value reset request
15
WEIGHT acquired request
Status word coding
15
14
13
12
11 10
9 8 7 6 5 4 3 2 1 0
POF F
S
Diagnostic error code
G/N
OS A P ZB R3 R2 R1
POF
Power On Flag. Indicates a return of power supply to the transmitter.
Flag is set to 1 by A200E and can be resetted to 0 by host by forcing
Coil #3
F
if = 1 indicates that unit is in FAULT
S
if = 1 indicates configuration in progress
Diagnostic err code
error code (see “self diagnostic” paragraph
G/N
if = 1 indicates that unit is in NET
ZB
if = 1 indicates that load is within Zero Band
R3
if = 1 indicates that relay #3 is ON
R2
if = 1 indicates that relay #2 is ON
R1
if = 1 indicates that relay #1 is ON
OS
if = 1 indicates that unit is out of scale (UL-OL)
P
if = 1 indicates that unit is in pause
A
if = 1 indicates that unit is in alarm