background image

 

23 

GENERAL SERVICE GUIDE Continued 
 

 

SYMPTOM POSSIBLE 

METHOD 

OF 

FINDING 

Running Cycle 
Too Long Or Unit 
Operates 
Continuously.

 

Refrigerant undercharged. 
Dirty filter or evaporator coil. 
Dirty or clogged condenser coil. 
Air or other non-condensables in system. 
Defective compressor. 
Restriction in suction and liquid line. 
Control contacts stuck. 

Check subcooling. 
Check filter, coil and airflow. 
Check coil and airflow. 
Check equalized high side pressure with equivalent outdoor temperature. 
See above – high suction pressure. 
Check for restrictions in refrigerant circuit. 
Check thermostat, shorts in wiring, slave relay compressor contactor. 

Supply Air 
Temperature 
Too High.

 

Refrigerant undercharge or leak in system. 
Evaporator plugged with dirt or ice. 
Improperly adjusted or defective expansion valve. 
Defective compressor. 
High discharge pressure. 
Airflow is too high. 

Check subcooling and check for leaks. 
Check evaporator, airflow and filter. 
Check superheat and adjust TXV, check bulb. 
Check compressor for proper operation. 
See above- high discharge pressure. 
Check external static pressure. 

Supply Air 
Temperature 
Too Low.

 

Airflow is too low. 
 
Return air temperature too low. 

Check evaporator coil, filter, check for closed dampers, grills, drive for loose parts,  
belts, misalignment, check external static pressure. 
Check entering air wet bulb conditions. 

Liquid Line  
Too Hot. 

Refrigerant undercharged. 
High discharge pressure. 

Charge by subcooling. 
See above – high discharge pressure. 

Liquid Line 
Frosted Or Wet.

 

Restriction in liquid line. 

Restriction upstream at point of frosting. 

Suction Line 
Frosting.

 

Insufficient evaporator airflow. 
Restriction in suction or liquid line. 
Malfunctioning or defective expansion valve. 

Check airflow, check drive for loose parts, belts, closed dampers. 
Restriction upstream at point of frosting. 
Check bulb of TXV. 

Blower Motor 
Not Running.

 

Improper wiring. 
Defective motor. 
Defective thermostat or control circuit. 
Motor off on overload protector. 

Check wiring diagram. 
Check motor controller. 
Check “R” and “G” Circuit. 
Allow motor to cool, check amperage. 

 
 

 
 
 
 
 
 
 
 
 

Содержание RCA051

Страница 1: ...3 11 4 RCA101 V HCA101 110 5 12 1 RCA141 V HCA141 142 3 11 5 RCA171 V HCA201 187 9 14 7 RCA201 V HCA201 217 0 14 6 RCA271 V HCA271 263 2 13 9 RCA361 V HCA361 311 6 13 3 RCA421 V HCA421 395 5 12 5 95...

Страница 2: ...s of the colors used Operational failure of this unit for any reason including but not limited to mechanical or electrical failure of devices internal or external to the unit loss of fuel such as natu...

Страница 3: ...rator at the air handling unit as possible The liquid line solenoid is factory installed on units with hot gas reheat Hot Gas Bypass Circuit Provided for capacity control by maintaining a constant suc...

Страница 4: ...rive sheaves connected to a 1725 rpm motor The blower has sealed ball bearings that do not require lubrication Blower Motor The blower motor operates at 1725 rpm The motor has sealed ball bearings tha...

Страница 5: ...lectric heater may be required Air Handler Model Heater kW Available V HCA051 1 9 V HCA071 1 12 V HCA141 1 25 V HCA201 5 39 V HCA271 5 50 V HCA361 10 60 Minimum 80 CFM per kW Table 4 UNIT LOCATION Con...

Страница 6: ...unit support at mounting location Install proper electrical power service and disconnect switch Provide drainage as necessary Maintain minimum clearance for airflow into and out of unit Inspection of...

Страница 7: ...1 030 0 5 1 090 0 6 1 160 0 7 1 500 680 0 3 780 0 3 870 0 4 960 0 5 1 040 0 6 1 100 0 7 1 100 650 0 2 770 0 3 860 0 3 940 0 4 1 020 0 5 1 090 0 6 1 160 0 6 VCA HCA 1 400 700 0 3 800 0 3 880 0 4 960 0...

Страница 8: ...8 DIMENSIONS...

Страница 9: ...9 DIMENSIONS Continued...

Страница 10: ...10 DIMENSIONS...

Страница 11: ...11 DIMENSIONS Continued...

Страница 12: ...LA MCA Max Fuse Size 208 230 1 60 4 4 6 15 208 230 3 60 2 0 3 15 460 3 60 1 0 2 15 1 2 380 415 3 50 1 5 2 15 208 230 1 60 5 4 7 15 208 230 3 60 2 8 4 15 460 3 60 1 4 2 15 3 4 380 415 3 50 2 1 3 15 208...

Страница 13: ...conjunction with the control for Hot Gas Reheat A remote system switch such as a timeclock or interlock may be used to energized the controls Once it is established that supply voltage is within the u...

Страница 14: ...14 TYPICAL FIELD WIRING DIAGRAM...

Страница 15: ...r handler is installed at a higher elevation than the compressor provide a vertical loop in the suction line adjacent to the air handler to a point at least to the top of the evaporator coil Do not in...

Страница 16: ...ic acid also decomposes the compressor lubrication oil causing sludge Great care should be exercised in keeping moisture out of the refrigeration system when installing tubing because an extremely sma...

Страница 17: ...17 FIELD WIRING DIAGRAM...

Страница 18: ...ove 70 75 degrees F Reduce the evaporator load lower entering airflow until the suction pressure lowers to the point at which bypass is desired 115 PSIG If the hot gas bypass was de energized to stop...

Страница 19: ...er is applied to the high pressure control and the adjustable time delay The time delay begins when power is applied to the timer After the time delay closes the circuit continues through the low pres...

Страница 20: ...er in a commercial split system New system must be evacuated as outlined on page 14 to remove air and non condensables in the system The liquid line drier will trap any moisture left in the system Sys...

Страница 21: ...d inlet clearances and for possible air re circulation Check high side equalized pressure reading with equivalent outdoor temperature Check calibration of switch Check discharge and liquid line pressu...

Страница 22: ...on of low ambient head pressure control Suction Pressure Too Low Refrigerant undercharge Blower running backwards Loose blower pulley or belts Defective or improperly adjusted expansion valve Dirty fi...

Страница 23: ...ilter Check superheat and adjust TXV check bulb Check compressor for proper operation See above high discharge pressure Check external static pressure Supply Air Temperature Too Low Airflow is too low...

Страница 24: ......

Страница 25: ...__________ WB _________ Design CFM ________________ Outdoor Air Inlet Temperature _____________ DB__________ WB _________ Outdoor Fan Discharge Air Temperature__________ DB ________ Suction Pressure _...

Страница 26: ...26 NOTES...

Страница 27: ...27 NOTES...

Страница 28: ...28...

Отзывы: