background image

 

3

PRODUCT DESCRIPTION 

THE CONDENSING UNIT CONSISTS OF THE 
FOLLOWING COMPONENTS: 

Compressor

: A single scroll compressor used in model 

sizes RCA051 – RCA201.  A tandem scroll is used in 
models RCA271-RCA421. All compressors have 
crankcase heaters and the motors are equipped with 
internal-overload protection  

Condenser:

 The condenser coils are aluminum plate 

finned formed on multiple rows of seamless copper tubing 
arranged in a staggered tube configuration.  

Condenser Air Fan(s)

: Each condenser air fan is a 

propeller type, electronically balanced and direct-driven. 
Condenser air is drawn through the coil(s) horizontally and 
discharged vertically. Therefore, heated air can not be re-
circulated. A vinyl coated fan guard is provided.  

Condenser Fan Motor(s):

 On standard RCA units the fan 

motors are single phase and are controlled by a low 
ambient head pressure control, which cycles the fan, or 
fans to maintain high side pressure. Units with optional hot 
gas reheat are different. One condenser fan is direct-
driven by a 1075 rpm single phase PSC fan motor, and it is 
controlled by a variable speed head pressure control. This 
electronic device is factory set for proper operation. The 
inherently protected motor has sealed ball bearings that do 
not require lubrication. On dual and multiple fan units, the 
other condenser fan motor(s) are three phase and are 
controlled by a separate low ambient control.  

REFRIGERANT CIRCUIT COMPONENTS 

Accumulator:

 A storage tank located in the suction line of 

the system. It separates the liquid refrigerant to protect the 
compressor from liquid slugging by allowing small amount 
of liquid refrigerant to boil away before entering the 
compressor.  

Filter-Drier (liquid)

: A filter used in the refrigerant line to 

remove moisture and small particles. 

High Pressure Safety Control

: A manual-reset high 

pressure control switch will stop the compressor if the 
system pressure exceeds 400 PSIG. This protects the 
compressor in case of blockage in the high side of the 
system. 

Low Pressure Control/Loss of Charge Protector:

 An 

automatic-reset low pressure control switch will stop the 
compressor if the low side of the system pressure drops 
below 60 PSIG. This is to protect the compressor in case 
of blockage in the low side of the system or loss of charge. 
This control is also used as an operating control-recycling 
pump-down. 

Dual Service Connections:

 Used for high and low 

pressure readings. 

24 Volt Pump Down Solenoid Valve:

 Shipped loose with 

the condensing unit and is to be field installed in the liquid 
line as close to the evaporator, at the air handling unit, as 
possible. The liquid line solenoid is factory installed on 
units with hot gas reheat. 

Hot Gas Bypass Circuit:

 Provided for capacity control by 

maintaining a constant suction pressure at the 
compressor. It consists of an adjustable pressure regulator 
which introduces compressor discharge gas into the 
evaporator, providing a false load. 

ELECTRIC CONTROLS 

Internally wired controls include; 

Compressor Anti-Short Cycle Timer: Prevents the 
compressor from rapid starting and stopping due to power 
interruptions. 

Fan and Compressor Motor Contactors or Starters:

 

These controls are rated for the connected load. 

24 Volt Transformer:

 Mounted in the sheet metal control 

panel. The 24 Volt control circuit includes a low voltage 
terminal board. 

Condenser Fan Cycling Head Pressure Control:

 The 

standard RCA unit utilizes this control to assure adequate 
head pressure control during low ambient conditions. This 
head pressure control system cycles the condenser fans 
off at 290 PSIG and on at 400 PSIG. This setting will be 
adequate for most systems. If trim adjustment is made, 
maintain wide differential to prevent rapid cycling of the fan 
motor.  

On systems with optional hot gas reheat this low ambient 
control is only used for the additional fan motor(s). The 
recommended settings are as follows; cut-off at 375 PSIG, 
and cut in at 455 PSIG. 

Variable Speed Condenser Head Pressure Control:

 

(furnished with hot gas reheat) Condenser head pressure 
is controlled by a variable speed control located in the 
compressor section. Through sensing of compressor 
discharge pressure, the voltage to the fan motor is 
adjusted to speed up or slow down the condenser fan 
speed. This action produces relatively constant discharge 
pressure at varying load and ambient conditions. The 
control is factory set to ensure consistent performance. 
(See Supplemental Instructions for Hot Gas Reheat for 
more information). 

Adjustable Ambient Thermostat (Compressor Lockout  
Thermostat):

 A remote field supplied and installed system 

switch, such as time clock or exhaust fan interlock, is 
required to start-stop the air handler blower motor and 
energize the controls. The compressor adjustable ambient 
lock-out thermostat controls the cooling operation at a 
setting between 65 and 70 degrees F. Operation of the 
compressor is thus limited to outside air temperatures 
above the setpoint.  

Typically, blower operation is continuous. The leaving air 
temperature will be maintained by compressor capacity 
control, accomplished through suction-pressure sensing, 
thus tracking the outside air temperature variations. The 
use of discharge air or space sensing devices (duct or 
room thermostats) to control the compressor will produce 
unpredictable results and is not recommended.

 

Содержание RCA051

Страница 1: ...3 11 4 RCA101 V HCA101 110 5 12 1 RCA141 V HCA141 142 3 11 5 RCA171 V HCA201 187 9 14 7 RCA201 V HCA201 217 0 14 6 RCA271 V HCA271 263 2 13 9 RCA361 V HCA361 311 6 13 3 RCA421 V HCA421 395 5 12 5 95...

Страница 2: ...s of the colors used Operational failure of this unit for any reason including but not limited to mechanical or electrical failure of devices internal or external to the unit loss of fuel such as natu...

Страница 3: ...rator at the air handling unit as possible The liquid line solenoid is factory installed on units with hot gas reheat Hot Gas Bypass Circuit Provided for capacity control by maintaining a constant suc...

Страница 4: ...rive sheaves connected to a 1725 rpm motor The blower has sealed ball bearings that do not require lubrication Blower Motor The blower motor operates at 1725 rpm The motor has sealed ball bearings tha...

Страница 5: ...lectric heater may be required Air Handler Model Heater kW Available V HCA051 1 9 V HCA071 1 12 V HCA141 1 25 V HCA201 5 39 V HCA271 5 50 V HCA361 10 60 Minimum 80 CFM per kW Table 4 UNIT LOCATION Con...

Страница 6: ...unit support at mounting location Install proper electrical power service and disconnect switch Provide drainage as necessary Maintain minimum clearance for airflow into and out of unit Inspection of...

Страница 7: ...1 030 0 5 1 090 0 6 1 160 0 7 1 500 680 0 3 780 0 3 870 0 4 960 0 5 1 040 0 6 1 100 0 7 1 100 650 0 2 770 0 3 860 0 3 940 0 4 1 020 0 5 1 090 0 6 1 160 0 6 VCA HCA 1 400 700 0 3 800 0 3 880 0 4 960 0...

Страница 8: ...8 DIMENSIONS...

Страница 9: ...9 DIMENSIONS Continued...

Страница 10: ...10 DIMENSIONS...

Страница 11: ...11 DIMENSIONS Continued...

Страница 12: ...LA MCA Max Fuse Size 208 230 1 60 4 4 6 15 208 230 3 60 2 0 3 15 460 3 60 1 0 2 15 1 2 380 415 3 50 1 5 2 15 208 230 1 60 5 4 7 15 208 230 3 60 2 8 4 15 460 3 60 1 4 2 15 3 4 380 415 3 50 2 1 3 15 208...

Страница 13: ...conjunction with the control for Hot Gas Reheat A remote system switch such as a timeclock or interlock may be used to energized the controls Once it is established that supply voltage is within the u...

Страница 14: ...14 TYPICAL FIELD WIRING DIAGRAM...

Страница 15: ...r handler is installed at a higher elevation than the compressor provide a vertical loop in the suction line adjacent to the air handler to a point at least to the top of the evaporator coil Do not in...

Страница 16: ...ic acid also decomposes the compressor lubrication oil causing sludge Great care should be exercised in keeping moisture out of the refrigeration system when installing tubing because an extremely sma...

Страница 17: ...17 FIELD WIRING DIAGRAM...

Страница 18: ...ove 70 75 degrees F Reduce the evaporator load lower entering airflow until the suction pressure lowers to the point at which bypass is desired 115 PSIG If the hot gas bypass was de energized to stop...

Страница 19: ...er is applied to the high pressure control and the adjustable time delay The time delay begins when power is applied to the timer After the time delay closes the circuit continues through the low pres...

Страница 20: ...er in a commercial split system New system must be evacuated as outlined on page 14 to remove air and non condensables in the system The liquid line drier will trap any moisture left in the system Sys...

Страница 21: ...d inlet clearances and for possible air re circulation Check high side equalized pressure reading with equivalent outdoor temperature Check calibration of switch Check discharge and liquid line pressu...

Страница 22: ...on of low ambient head pressure control Suction Pressure Too Low Refrigerant undercharge Blower running backwards Loose blower pulley or belts Defective or improperly adjusted expansion valve Dirty fi...

Страница 23: ...ilter Check superheat and adjust TXV check bulb Check compressor for proper operation See above high discharge pressure Check external static pressure Supply Air Temperature Too Low Airflow is too low...

Страница 24: ......

Страница 25: ...__________ WB _________ Design CFM ________________ Outdoor Air Inlet Temperature _____________ DB__________ WB _________ Outdoor Fan Discharge Air Temperature__________ DB ________ Suction Pressure _...

Страница 26: ...26 NOTES...

Страница 27: ...27 NOTES...

Страница 28: ...28...

Отзывы: