background image

 

5

PRODUCT DESCRIPTION Continued

 

OPTIONAL FEATURES  

(which may be furnished with the system) 

Heat Recovery Water Heater (Desuperheater):

 By 

factory installing a refrigerant- to- water heat exchanger on 
top of the condensing unit,

 

and piping the refrigerant side 

into the compressor discharge, waste heat recovery is 
accomplished in a straight forward manner. The two water 
connections are stubbed out for field piping to other heat 
recovery units or directly to the domestic hot water supply 
which also must include a circulating pump, temperature 
control valve, and storage tank.. 

Sure-Trip:

 Phase loss and low voltage safety monitor 

automatically stops the unit whenever a phase is lost, 
phases are out-of-sequence, or when voltage level drops 
too low. Restart is automatic, with time delay when proper 
power supply conditions are restored. 

Hot Gas Reheat Coil: 

For closer humidity control, a one 

row copper tube, aluminum fin (12 fins per inch) hot gas 
reheat system can be factory installed. The system 
includes the heat reclaim coil, located downstream from 
the evaporator coil in the air handler, condenser variable 
speed head pressure control, check valve. Available 
reheat capacity is 7,000 btu per ton. A field adjustable 
thermostat controls the hot gas reheat solenoid valve. 

The Heat Recovery Water Heater Coil is not 
recommended to be used with units equipped with Hot 
Gas reheat.

 

Clogged Filter Indicator:

 

Dirty or clogged filters are red 

flagged by the indicator when the preset pressure 
differential across the filters is reached. The indicator is 
field installed and manual-reset. 

Electric Heaters: Add-on electric heaters are available in a 
wide kilowatt range. The heater is shipped loose for field 
mounting to the supply air duct connection of the air 
handler. Heaters are furnished with open coil heating 
elements of high grade nickel-chromium, auto reset 
primary and manual reset secondary safety devices, 
differential air pressure switch, and branch circuit fusing 
per NEC/UL. A hinged cover control panel is provided on 
the welded galvanized steel cabinet. A separate field 
installed and wired system switch and disconnect for the 
electric heater may be required. 
 

Air Handler Model 

Heater kW* Available 

V/HCA051 

1-9 

V/HCA071 

1-12 

V/HCA141 

1-25 

V/HCA201 

5-39 

V/HCA271 

5-50 

V/HCA361 

10-60 

 *Minimum 80 CFM per kW 

Table 4 

 

 
UNIT LOCATION 

Condensing Unit Location 

Locate as near as possible to the inside section in order to 
keep connecting refrigerant tubing lengths to minimum and 
thus minimize loss of capacity due to long lines 

(see Table 

9  Notes 5 & 6)

An intake louver protects the service end and clearance at 
this point should be maintained. A 36" clearance must be 
allowed for access to the compressor and electrical panel. 
A 24" clearance must be maintained  for the air inlet to the 
condenser coil(s). 

Do not locate the unit under an overhang that will short 
circuit hot air to the coil intakes. 

When installed at ground level, the unit should be mounted 
on a level concrete slab which should extend at least 2" 
beyond the unit on all sides. The top of the slab should be 
2" above the ground level. The depth of the slab below the 
ground level and its structural design is governed by the 
type of soil and climatic conditions. The slab must not be in 
contact with any part of the building wall or foundation. The 
space between the slab and building wall prevents the 
possibility of transmitting vibration to the building. 

 

The dimensions of the slab or roof mount should be 
checked and verified before the equipment arrives. Unit 
supports, roof opening, roof curb flashing, drain 
requirements, and electric locations are important to a 
good installation. 

When installing the equipment on top of a building, the 
following should be considered: 

Structural members supporting the unit must be sufficiently 
strong for the weight of the unit and mounting rails. 

Locate the unit as near as possible to the center of the 
area to be environmentally controlled.  Sufficient clearance 
must be available for service, edge of roof, other units, or 
hazards. 

The condenser air inlet and discharge air must be 
unobstructed by overhang, walls, or other equipment. 
Avoid locations next to exhaust fans or flues. 

Select a location where external water drainage cannot 
collect around the unit. 

Locate the unit so roof runoff water does not pour directly 
on the unit. Provide gutter or other shielding at roof level. 

Where snowfall is anticipated, mount the unit above the 
maximum snow depth for the area.

 

 

 
 
 
 

 

 

Содержание RCA051

Страница 1: ...3 11 4 RCA101 V HCA101 110 5 12 1 RCA141 V HCA141 142 3 11 5 RCA171 V HCA201 187 9 14 7 RCA201 V HCA201 217 0 14 6 RCA271 V HCA271 263 2 13 9 RCA361 V HCA361 311 6 13 3 RCA421 V HCA421 395 5 12 5 95...

Страница 2: ...s of the colors used Operational failure of this unit for any reason including but not limited to mechanical or electrical failure of devices internal or external to the unit loss of fuel such as natu...

Страница 3: ...rator at the air handling unit as possible The liquid line solenoid is factory installed on units with hot gas reheat Hot Gas Bypass Circuit Provided for capacity control by maintaining a constant suc...

Страница 4: ...rive sheaves connected to a 1725 rpm motor The blower has sealed ball bearings that do not require lubrication Blower Motor The blower motor operates at 1725 rpm The motor has sealed ball bearings tha...

Страница 5: ...lectric heater may be required Air Handler Model Heater kW Available V HCA051 1 9 V HCA071 1 12 V HCA141 1 25 V HCA201 5 39 V HCA271 5 50 V HCA361 10 60 Minimum 80 CFM per kW Table 4 UNIT LOCATION Con...

Страница 6: ...unit support at mounting location Install proper electrical power service and disconnect switch Provide drainage as necessary Maintain minimum clearance for airflow into and out of unit Inspection of...

Страница 7: ...1 030 0 5 1 090 0 6 1 160 0 7 1 500 680 0 3 780 0 3 870 0 4 960 0 5 1 040 0 6 1 100 0 7 1 100 650 0 2 770 0 3 860 0 3 940 0 4 1 020 0 5 1 090 0 6 1 160 0 6 VCA HCA 1 400 700 0 3 800 0 3 880 0 4 960 0...

Страница 8: ...8 DIMENSIONS...

Страница 9: ...9 DIMENSIONS Continued...

Страница 10: ...10 DIMENSIONS...

Страница 11: ...11 DIMENSIONS Continued...

Страница 12: ...LA MCA Max Fuse Size 208 230 1 60 4 4 6 15 208 230 3 60 2 0 3 15 460 3 60 1 0 2 15 1 2 380 415 3 50 1 5 2 15 208 230 1 60 5 4 7 15 208 230 3 60 2 8 4 15 460 3 60 1 4 2 15 3 4 380 415 3 50 2 1 3 15 208...

Страница 13: ...conjunction with the control for Hot Gas Reheat A remote system switch such as a timeclock or interlock may be used to energized the controls Once it is established that supply voltage is within the u...

Страница 14: ...14 TYPICAL FIELD WIRING DIAGRAM...

Страница 15: ...r handler is installed at a higher elevation than the compressor provide a vertical loop in the suction line adjacent to the air handler to a point at least to the top of the evaporator coil Do not in...

Страница 16: ...ic acid also decomposes the compressor lubrication oil causing sludge Great care should be exercised in keeping moisture out of the refrigeration system when installing tubing because an extremely sma...

Страница 17: ...17 FIELD WIRING DIAGRAM...

Страница 18: ...ove 70 75 degrees F Reduce the evaporator load lower entering airflow until the suction pressure lowers to the point at which bypass is desired 115 PSIG If the hot gas bypass was de energized to stop...

Страница 19: ...er is applied to the high pressure control and the adjustable time delay The time delay begins when power is applied to the timer After the time delay closes the circuit continues through the low pres...

Страница 20: ...er in a commercial split system New system must be evacuated as outlined on page 14 to remove air and non condensables in the system The liquid line drier will trap any moisture left in the system Sys...

Страница 21: ...d inlet clearances and for possible air re circulation Check high side equalized pressure reading with equivalent outdoor temperature Check calibration of switch Check discharge and liquid line pressu...

Страница 22: ...on of low ambient head pressure control Suction Pressure Too Low Refrigerant undercharge Blower running backwards Loose blower pulley or belts Defective or improperly adjusted expansion valve Dirty fi...

Страница 23: ...ilter Check superheat and adjust TXV check bulb Check compressor for proper operation See above high discharge pressure Check external static pressure Supply Air Temperature Too Low Airflow is too low...

Страница 24: ......

Страница 25: ...__________ WB _________ Design CFM ________________ Outdoor Air Inlet Temperature _____________ DB__________ WB _________ Outdoor Fan Discharge Air Temperature__________ DB ________ Suction Pressure _...

Страница 26: ...26 NOTES...

Страница 27: ...27 NOTES...

Страница 28: ...28...

Отзывы: