background image

 

19

CAPACITY CONTROL 

Hot Gas Bypass 

The purpose of the hot gas bypass refrigerant circuit is to 
maintain evaporator temperature above freezing (32 
degrees), thus saving the compressor from failure and 
controlling capacity. Compressor capacity modulation by 
means of hot gas bypass is used where normal 
compressor cycling or the use of cylinder unloading alone 
may not be sufficient. This bypass valve is used on all  
 
RCA units. It must be field adjusted. The bypass valve 
opens at the recommended setting and can bypass up to 
50% to the evaporator. Due to the reduced power 
consumption at lower suction pressures, the hot gas 
bypass valve should be adjusted to bypass at the minimum 
suction pressure within the compressors operating limits. 
Be sure the hot gas setting is lower than the unloading 

pressure control when both are used (semi- hermetic). If 
the pressure setting of the cylinder unloading is increased, 
the hot gas bypass setting must also be increased. 
In order to make field adjustments to this regulator, it may 
require simulating a light load condition. Connect a 
pressure gauge to the suction line and block the entering 
air to the evaporator. Suction pressure will drop and the 
valve should begin to open at approximately 62 PSIG. It 
has a range of 6 PSIG and will be fully open at 56 PSIG. 
The hot gas bypass valve will get warm to the touch when 
the valve begins to open. To adjust, remove the cap and 
turn the adjusting stem clockwise to reduce the setpoint 
and counterclockwise to increase the setpoint. Allow 5 
minutes between adjustments to allow the system to 
stabilize. 

 

SEQUENCE OF OPERATION 

Control Sequence  

Refer to typical wiring diagrams for these units. 
The field supplied system switch is closed. The “R” circuit 
from the transformer is fed through the system switch to 
the coil of the blower motor contactor. This energizes the 
coil and closes the contacts which brings power to the 
blower motor.  
From the low voltage terminal board  “R” is connected to 
the “G” by the closing of the system switch. “G” is a series 
circuit through the compressor lockout thermostat. If the 
outdoor temperature is above the setting of the 
compressor lockout thermostat, “G” is connected to the “Y” 
terminal and continues to the coil of the cooling relay. This 
energizes the contacts of the cooling pilot relay which 
energizes the hot gas bypass solenoid. Another set of 
contacts from this relay apply power to the “A” terminal of 
the low voltage terminal board. This energizes the coil of 
the liquid line solenoid valve. In a parallel circuit power is 
applied to the high pressure control, and the adjustable 
time delay. The time delay begins when power is applied 
to the timer.  
After the time delay closes, the circuit continues through 
the low pressure switch, and the compressor overload 
protection module (if supplied). The coil of the compressor 
contactor is now energized. At this time the coil of the 
contactor for the condenser fans is fed through the low 
ambient control switch (units with reheat use the variable 
speed control). The contacts close and power is applied to 
the compressor and fan motors. 
On systems with semi-hermetic compressors, the 
compressor contactor and condenser fan contactor(s) are 
in a series circuit with the oil failure control, and the 
optional phase monitor. The unloading pressure control will 
energize and de-energize the unloader solenoid on the 
compressor as needed. 
 

 

Systems with hot gas reheat (optional), power is applied 
from the reheat thermostat from “Y- H” to the reheat valve 
relay. The reheat thermostat is to be set between 65-70 
degrees F. When the outlet or leaving air drops below this 
setting the thermostat contacts will close and energize  the 
reheat valve relay. The reheat refrigerant circuit is now 
initiated.  
It should be noted that the high pressure control has a 
manual reset feature. The low pressure cutout is set at 60 
PSIG and is automatic reset. Experience has indicated that 
fast cycling on the low pressure control is due to low 
refrigerant charge, dirty filters, dirty evaporator coil, loose  
belts, or reduced air flow and will ruin contactor points and 
compressors. 

Operating Pressures and Temperatures 

This information should only be used as a guide, due to 
the diversity of applications and various conditions (wet 
bulb and dry bulb) that may be present in the field; A 
properly charged system will have varied suction and 
discharge pressures depending on whether the unit is 
equipped with unloading, hot gas reheat, or in hot gas 
bypass. The head pressure will be controlled by the low 
ambient control bringing the fan motors on to lower and 
turning the fans off to raise the head pressure. The suction 
pressures will vary up and down reacting to the outdoor 
(WB) temperature and will depend on whether the unit is in 
hot gas bypass or unloaded.  The head pressure will vary 
from 350-400 PSIG at average (85-95 degree DB) outdoor 
temperatures. 
The temperature difference between the return air (outside 
temperature DB) and the supply air should be 
approximately 30-40 degrees F at average entering (WB) 
conditions. CFM must be correct. The sub-cooling should 
be around 15 degrees at 75 degrees F and as low as 5 
degrees at 105 degrees F. The superheat should be 
approximately 18-20 degrees F. at the suction line in the 
condensing unit. 

Содержание RCA051

Страница 1: ...3 11 4 RCA101 V HCA101 110 5 12 1 RCA141 V HCA141 142 3 11 5 RCA171 V HCA201 187 9 14 7 RCA201 V HCA201 217 0 14 6 RCA271 V HCA271 263 2 13 9 RCA361 V HCA361 311 6 13 3 RCA421 V HCA421 395 5 12 5 95...

Страница 2: ...s of the colors used Operational failure of this unit for any reason including but not limited to mechanical or electrical failure of devices internal or external to the unit loss of fuel such as natu...

Страница 3: ...rator at the air handling unit as possible The liquid line solenoid is factory installed on units with hot gas reheat Hot Gas Bypass Circuit Provided for capacity control by maintaining a constant suc...

Страница 4: ...rive sheaves connected to a 1725 rpm motor The blower has sealed ball bearings that do not require lubrication Blower Motor The blower motor operates at 1725 rpm The motor has sealed ball bearings tha...

Страница 5: ...lectric heater may be required Air Handler Model Heater kW Available V HCA051 1 9 V HCA071 1 12 V HCA141 1 25 V HCA201 5 39 V HCA271 5 50 V HCA361 10 60 Minimum 80 CFM per kW Table 4 UNIT LOCATION Con...

Страница 6: ...unit support at mounting location Install proper electrical power service and disconnect switch Provide drainage as necessary Maintain minimum clearance for airflow into and out of unit Inspection of...

Страница 7: ...1 030 0 5 1 090 0 6 1 160 0 7 1 500 680 0 3 780 0 3 870 0 4 960 0 5 1 040 0 6 1 100 0 7 1 100 650 0 2 770 0 3 860 0 3 940 0 4 1 020 0 5 1 090 0 6 1 160 0 6 VCA HCA 1 400 700 0 3 800 0 3 880 0 4 960 0...

Страница 8: ...8 DIMENSIONS...

Страница 9: ...9 DIMENSIONS Continued...

Страница 10: ...10 DIMENSIONS...

Страница 11: ...11 DIMENSIONS Continued...

Страница 12: ...LA MCA Max Fuse Size 208 230 1 60 4 4 6 15 208 230 3 60 2 0 3 15 460 3 60 1 0 2 15 1 2 380 415 3 50 1 5 2 15 208 230 1 60 5 4 7 15 208 230 3 60 2 8 4 15 460 3 60 1 4 2 15 3 4 380 415 3 50 2 1 3 15 208...

Страница 13: ...conjunction with the control for Hot Gas Reheat A remote system switch such as a timeclock or interlock may be used to energized the controls Once it is established that supply voltage is within the u...

Страница 14: ...14 TYPICAL FIELD WIRING DIAGRAM...

Страница 15: ...r handler is installed at a higher elevation than the compressor provide a vertical loop in the suction line adjacent to the air handler to a point at least to the top of the evaporator coil Do not in...

Страница 16: ...ic acid also decomposes the compressor lubrication oil causing sludge Great care should be exercised in keeping moisture out of the refrigeration system when installing tubing because an extremely sma...

Страница 17: ...17 FIELD WIRING DIAGRAM...

Страница 18: ...ove 70 75 degrees F Reduce the evaporator load lower entering airflow until the suction pressure lowers to the point at which bypass is desired 115 PSIG If the hot gas bypass was de energized to stop...

Страница 19: ...er is applied to the high pressure control and the adjustable time delay The time delay begins when power is applied to the timer After the time delay closes the circuit continues through the low pres...

Страница 20: ...er in a commercial split system New system must be evacuated as outlined on page 14 to remove air and non condensables in the system The liquid line drier will trap any moisture left in the system Sys...

Страница 21: ...d inlet clearances and for possible air re circulation Check high side equalized pressure reading with equivalent outdoor temperature Check calibration of switch Check discharge and liquid line pressu...

Страница 22: ...on of low ambient head pressure control Suction Pressure Too Low Refrigerant undercharge Blower running backwards Loose blower pulley or belts Defective or improperly adjusted expansion valve Dirty fi...

Страница 23: ...ilter Check superheat and adjust TXV check bulb Check compressor for proper operation See above high discharge pressure Check external static pressure Supply Air Temperature Too Low Airflow is too low...

Страница 24: ......

Страница 25: ...__________ WB _________ Design CFM ________________ Outdoor Air Inlet Temperature _____________ DB__________ WB _________ Outdoor Fan Discharge Air Temperature__________ DB ________ Suction Pressure _...

Страница 26: ...26 NOTES...

Страница 27: ...27 NOTES...

Страница 28: ...28...

Отзывы: