EVO S
, Installation, Commisioning and Servicing Instructions
67
EN
Diagram: EVO S-3
page 5 / 6
F. SPECIFIC START-UP PROCEDURE
"
Correctly install and connect the electrical connections.
"
Make the settings below in "specialist" mode:
Line No. Value
• Time and date
menu
Set the time
Hour / minute (1)
HH.MM
Set the date
Day / month (2)
DD.MM
Set the year
Year (3)
YYYY
•
Configuration
menu
Configure the secondary flow sensor
BX2 sensor input (5931)
B10 line output sensor
Start up heating circuit 1
Heating circuit 1 (5710)
Start
Start up heating circuit 2
Heating circuit 2 (5715)
Start
Start up heating circuit 3
Heating circuit 3 (5721)
Start
Configure the alarm output
Relay output QX1 (5890)
Alarm circuit K10
Configure the DHW tank pump output
Relay output QX2 (5891)
DHW pump Q3
Configure the direct circuit pump Q2
Relay output QX3 (5892)
Pump CC1 Q2
Configure the extension modules
Extension module function 1 (6020)
Heating circuit 2
Extension module function 2 (6021)
Heating circuit 3
Save the sensors so that they are taken
into account by the system
Save sensor (6200)
Yes (switches back to
no automatically)
OK
OK
Short press
Press for 3 seconds
End user
Start-up
Specialist
OEM
IMPORTANT:
configure the switches on the AGU 2.550 extension modules.
Содержание EVO S 100
Страница 2: ......
Страница 13: ... EVO S Installation Commisioning and Servicing Instructions 13 EN ...
Страница 44: ...EVO S Installation Commisioning and Servicing Instructions EN 44 Figure 19 Wiring diagram ...
Страница 45: ...EVO S Installation Commisioning and Servicing Instructions 45 EN ...
Страница 149: ...EVO S Installation Commisioning and Servicing Instructions 149 EN ...
Страница 150: ...EVO S Installation Commisioning and Servicing Instructions EN 150 ...
Страница 151: ...EVO S Installation Commisioning and Servicing Instructions 151 EN ...
Страница 152: ...EVO S Installation Commisioning and Servicing Instructions EN 152 ...
Страница 153: ...EVO S Installation Commisioning and Servicing Instructions 153 EN ...