EVO S
, Installation, Commisioning and Servicing Instructions
EN
100
OPTIMISATION
page 4 / 4
DHW CIRCUIT OPTIMISATION
Line No. Value
• DHW tank
menu
Adjust the over value
Start setpoint T° over-value (5020)
16 °C
•
Configuration
menu
Activate the heating circuits' frost
protection mode
Installation frost protection (6120)
on
Setting the anti-legionella cycle (if desired)
• Domestic hot water
menu
Activate anti-legionella mode
Anti-legionella function (1640)
stop / periodic / fixed
day of the week
Choice of repetition. From daily to every 7 days. 1641 = periodic
Periodical anti-legionella function (1641)
1 to 7 days
Choice of day of the week if 1641 = fixed weekday
Legionella function day week (1642)
Monday...Sunday
Anti-legionella launch time
Times of anti-legionella operation (1644)
00:00
Heating T° setpoint for anti-legionella
function
Anti-legionella setpoint (1645)
As needed (°C)
Anti-legionella T° holding time
Anti-legionella function duration (1646)
As needed (min)
Содержание EVO S 100
Страница 2: ......
Страница 13: ... EVO S Installation Commisioning and Servicing Instructions 13 EN ...
Страница 44: ...EVO S Installation Commisioning and Servicing Instructions EN 44 Figure 19 Wiring diagram ...
Страница 45: ...EVO S Installation Commisioning and Servicing Instructions 45 EN ...
Страница 149: ...EVO S Installation Commisioning and Servicing Instructions 149 EN ...
Страница 150: ...EVO S Installation Commisioning and Servicing Instructions EN 150 ...
Страница 151: ...EVO S Installation Commisioning and Servicing Instructions 151 EN ...
Страница 152: ...EVO S Installation Commisioning and Servicing Instructions EN 152 ...
Страница 153: ...EVO S Installation Commisioning and Servicing Instructions 153 EN ...