EVO S
, Installation, Commisioning and Servicing Instructions
27
EN
Figure 8 - Dimensioning recommendations
4.3.3. Connection to a B23P chimney
B23P type connection:
Air from the installation premises, gas evacuation through the roof via a
pressurised duct.
IMPORTANT:
The use of the "Chimney Adaptor" accessory is mandatory to connect
a EVO S boiler to a B23P chimney duct. The table below shows the
accessories available for each boiler type.
IMPORTANT:
Check that the boiler installation premises have high and low
ventilation, that it conforms to current regulations and that it is not
obstructed.
The A dimension indicates the height
of the chimney adapter when fully
inserted relative to the
upper panel of
the boiler.
A