EVO S
, Installation, Commisioning and Servicing Instructions
EN
136
For
VFC
signals
Contacts on X1 L (1) and QX21 (7) can be used for the following:
Boiler flame on/Boiler demand (closed contact)
Contacts on X1 L (1) and QX22 (5) can be used for the following:
Fault errors (closed contact)
E133 flame failure
E110 temperature high limit
E132 low gas pressure
E132 flue or condensate blocked.
For
mains supply
230V signals, connect the white lead into X1 brown wire
to L (1) and blue wire N (2).
Connect the opposite end of the cable into terminal 17 live, and terminal 18
neutral, as shown.
Contacts on X1 N (6) and QX21 (7) 230V can be used for the following:
Boiler flame on/Boiler demand (closed contact)
Contacts on N (4) and QX22 (5) 230V can be used for the following:
Fault errors (closed contact)
E133 flame failure
E110 temperature high limit
E132 low gas pressure
E132 flue or condensate blocked.
12.1.2.2.
Extension module configurationt
12.1.3. UIN 23579 HC EXTENSION MODULE
Line No.
Parameter
Settings
6020
Function extension module 1
Multifunctional
6030
Relay output QX21 module 1
Status information K36
6031
Relay output QX22 module 1
Alarm output K10
Содержание EVO S 100
Страница 2: ......
Страница 13: ... EVO S Installation Commisioning and Servicing Instructions 13 EN ...
Страница 44: ...EVO S Installation Commisioning and Servicing Instructions EN 44 Figure 19 Wiring diagram ...
Страница 45: ...EVO S Installation Commisioning and Servicing Instructions 45 EN ...
Страница 149: ...EVO S Installation Commisioning and Servicing Instructions 149 EN ...
Страница 150: ...EVO S Installation Commisioning and Servicing Instructions EN 150 ...
Страница 151: ...EVO S Installation Commisioning and Servicing Instructions 151 EN ...
Страница 152: ...EVO S Installation Commisioning and Servicing Instructions EN 152 ...
Страница 153: ...EVO S Installation Commisioning and Servicing Instructions 153 EN ...