![Acrel AID150 Скачать руководство пользователя страница 8](http://html.mh-extra.com/html/acrel/aid150/aid150_installation-and-operation-manual_3046841008.webp)
4
Remotely setting the insulation resistance alarm value, load current alarm value and transformer
temperature alarm value of each system insulation monitoring device, and remotely activated
self-test of the insulation monitor.
When insulation faults, overload, excessive temperature rise of the transformer or wiring faults
occured in any of the monitored system, centralized alarm and display device will provide
corresponding audible and visual alarm signals, and can manually mute the alarm sound.
Events logging function, which is convenient for operation personnel to analyze the operation
conditions of system and promptly eliminate the faults, and can save maximum of 20 latest
records;
2.6 Function features of HDR-60-24 power supply device
AC 220V input, DC 24V output, with max output power of 60W;
Used for the DC 24V power supply for AIM-M300 series medical intelligent insulation monitoring
device, AIL150/AIL160 series insulation fault locator, AID150 centralized alarm and display
device and other devices.
2.7 Function features of AKH-0.66P26 current transformer
The maximum measurable current is 60A, and the transformation change ratio is 2000:1;
Work with the AIM-M300 series insulation monitoring device to measure the load current of
isolation transformer.
3 Reference standard
◆
IEC 60364-7-710: 2002
Building electrical installations section 7-710: Requirements for special
installations or locations----medical locations
;
◆
IEC 61557-8-2014
Electrical safety of low voltage distribution system below AC 1000V and DC
1500V, Test, measurement or monitoring equipment for protection test section 8: Insulation
monitoring device for IT systems
;
◆
IEC 61557-9-2014
Electrical safety of low voltage distribution system below AC 1000V and DC
1500V, Test, measurement or monitoring equipment for protection test section 9: insulation fault
positioning equipment for IT systems
;
◆
IEC61558-1: 2009
Safety of power transformers, power supplies, reactors and similar products
section 1: General requirements and tests
;
◆
IEC61558-2-15: 2011
Safety of power transformers, power supplies and similar products section