to enter other settings item, then change the password number by "Up " or "Down " button, then press
"Enter" button to confirm it. Press "Return" button to save and exit programming mode. Examples
of operations are as follows:
(4) Alarm parameter setting
Alarm parameters are used to set the parameters of system insulation alarm, current overload alarm
and transformer temperature alarm, which are similar to the steps of "system password setting".
The following only provides examples for setting insulation alarm value, current overload alarm
value and temperature alarm value.The insulation alarm value is set to 50kΩ, and the current alarm
value is set to 14A and the temperature alarm value is set to 70℃. The procedure is as follows:
ENTER
Set Comms
Set Alarm
Set Clock Set Misc.
Res :
040
kΩ Curr:035A
Temp:060℃
UP/DOWN
Res :
050
kΩ Curr:035A
Temp:060℃
Res :
050
kΩ Curr:035A
Temp:060℃
ENTER
UP/DOWN
Res : 050kΩ Curr:
035
A
Temp:060℃
ENTER
Res : 050kΩ Curr:
035
A
Temp:060℃
Res : 050kΩ Curr:
014
A
Temp:060℃
UP/DOWN
ENTER
Res : 050kΩ Curr:
014
A
Temp:060℃
UP/DOWN
Res :050kΩ Curr:014A
Temp:
060
℃
Res :050kΩ Curr:014A
Temp:
060
℃
ENTER
UP/DOWN
Res :050kΩ Curr:014A
Temp:
070
℃
TEST
save/quit
2012-10-10 12:29:43
R
>999
KΩ T=023
℃
I = 0.0 A (00%)
2012-10-10 12:29:43
R
>999
KΩ T=023
℃
I = 0.0 A (00%)
ENTER
UP/DOWN
Set Comms
Set Alarm
Set Clock Set Misc.
UP/DOWN
Set Comms Set Alarm
Set Clock
Set Misc.
Password:
0001
LCD: 00
B. Light: On Clear:N
Password:
0001
LCD: 00
B. Light: On Clear:N
UP/DOWN
Password:
0002
LCD: 00
B. Light: On Clear:N
ENTER
Password:
0002
LCD: 00
B. Light: On Clear:N
Set Comms Set Alarm
Set Clock
Set Misc.
UP/DOWN
Save Setting
?
Y
N
UP/DOWN
Save Setting
?
Y
N
Enter
ENTER
TEST
ENTER
2012-10-10 12:29:43
R
>999
KΩ T=023
℃
I = 0.0 A (00%)
Input the password
0000
Input the password
000
1