7
current
monitoring
Alarm Value
5…60A
Communication protocol
CAN,customize
Measuring
accuracy
±5%
RS485,Modbus-RTU
Locating
note
Measuring voltage
±12V
Measuring current
≤50
μA
Note:
AIM-M300 insulation monitoring device doesn’t support locating function. When need fault
locating function, please select AIM-M300/SG.
4.3 Technical parameters of AIL150-4/AIL150-8 /AIL160-4test signal generator
Refer to Table 4.
Table 4 Technical Parameters ofAIL150-4/AIL150-8/AIL160-6
Item
Technical parameters
AIL150-4/AIL150-8/AIL160-6
Auxiliary
power supply
Voltage
DC 18…36V
Maximum power consumption
≤2VA
Monitored
system
Rated voltage
0…242 VAC
Rated frequency
45… 60Hz
Fault locating
Maximum circuit
4,8,6 Loops
Response time
≤5s
Communication
Mode
CAN
communication
Protocol
Self-defined protocol
4.4 Technical parameters of AID150 centralized alarm and display device
Refer to Table 5.
Table 5 Technical Parameters of AID150 Centralized Alarm and Display Device
Type
Parameters
AID150
AUX POWER
Voltage
DC 24V
Power consumption
≤0.6W
Insulation Resistance Display Range
0…999kΩ
Insulation alarm range
50…999kΩ
Transformer Output Current Display
Percentage
Current alarm range
14A、18A、22A、28A、35A、45A
Temperature alarm range
0…+200℃
Alarm mode
Audiable and visible alarm