30
7
0006H high
byte
Hour
R/W
0-23
Word
0006H
low
byte
Minute
R/W
0-59
8
0007H high
byte
Second
R/W
0-59
Word
0007H
low
byte
Reserve
R
9
0008H
Insulation
resistance
R/W
10-999(Unit is KΩ)
Word
10
0009H
Load current
R/W
0-500(Unit is 0.1A)
Word
11
000AH
Transformer
temperature
R/W
40-140(Unit is℃)
Word
12
000BH high
byte
Fault circuit
1-8
Word
000BH
low
byte
Fault type
R
Bit0:1 Insulation resistance
fault
Bit1:1 Overload fault
Bit2:1 Transformer overheat
fault
Bit3:1 L1 or L2
disconnection
fault
Bit4:1 PE or KE
disconnection
fault
Bit5:1 Temperature sensor
disconnection fault
Bit6:1 Current transformer
disconnection fault (preset)
Bit7:1 Device fault
13-
16
000CH-000FH Preset
17
0010H
Insulation
resistance
set
value
R
10-999(Unit is kΩ)(Default
value is 50)
Word