ASD SERIES INSTALLATION AND OPERATION MANUAL 

 QUICK-START INSTRUCTIONS 

Also see Section 3 

– Important Application Information on page 5. 

 

Important:

 You must read these simplified instructions before proceeding. These instructions are to be used as a reference only and are not 

intended to replace the details provided herein. You must read the Safety Warnings on page 5 before proceeding. 

 

Reconditioning the Bus Capacitors: 

If this drive has been in storage for over one year, it is necessary to recondition the power supply bus 

capacitors. To recondition the bus capacitors, apply the AC Line, with the drive in the Stop Mode, for a minimum of one hour. Not following this 
procedure will cause the bus capacitors to fail. 

 

 

WARNING! High Voltage! 

Disconnect the main power before making connections to the control. Do not depend on the POWER or STATUS 

LEDs, located on the front cover, to no longer be illuminated as a guaranteed power off condition. 

 
1.1 

– MOUNTING INSTRUCTIONS 

See Section 5 on page 11. 
 

1.2 

– AC LINE INPUT FUSING 

It  is  recommended  that  a  fuse(s)  or  circuit  breaker  be 
installed in the AC Line. Fuse each conductor that is not at 
ground  potential.  For  the  recommended  fuse  size,  see 
Table 1 on page 7. Also see Section 6 on page 13. 
 

1.3 

– AC LINE INPUT CONNECTION 

Connect the AC Line input to Terminal Block TB1, as shown 
in Figure 1. Also see Section 7.1 on page 13. 
 

GFCI Operation: 

The drives are jumper selectable (J12) for 

standard and sensitive GFCIs. 
 

 

CAUTION!

 The rated AC Line voltage of the drive must 

match the actual AC Line input voltage. On ASD-24D, 27D 
the  setting  of  Jumper  J1  must  match  the  actual  AC  Line 
input voltage. 
 

ASD-24D,  27D,  29  (1P):

  Designed  to  accept  1-phase 

(Terminals L1, L2) AC Line input only. Rated for 208/230 Volt AC Line input with Jumper J1 set to the "230V" position (factory setting). Rated 
for 115 Volt AC Line input with Jumper J1 set to the "115V" position. ASD-27D is rated for 1½ HP maximum with 115 Volt AC Line input and     
2 HP maximum with 208/230 Volt AC Line input. 
 

ASD-29:

 Designed to accept 1-phase (Terminals L1, L2) or 3-phase (Terminals L1, L2, L3) AC Line input. Rated for 208/230 Volt AC Line input 

only. Rated for 2 HP maximum with 1-phase AC Line input and 3 HP maximum with 3-phase AC Line input. 
 

ASD-45, 48:

 Designed to accept 3-phase (Terminals L1, L2, L3) AC Line input only. Rated for 400/460 Volt AC Line input only. 

 

1.4 

– MOTOR CONNECTION 

Connect the motor to Terminal Block TB1 Terminals U, V, W, as shown in Figure 1. See Section 7.2 on page 14. Motor cable length should not 
exceed 100 ft. (30 m) 

– special reactors may be required – contact Technical Support. 

 

1.5 

– GROUND CONNECTION 

Connect the ground wire (earth) to the ground screw, as shown in  Figure 1. See Section 7.3 on page 14. Be sure the motor is also properly 
grounded. 
 

1.6 

– 60 Hz AND 50 Hz MOTOR OPERATION 

The drive is factory set for 60 Hz motor operation (Jumper J4 set to the "1X" position and Jumper J5 set to the "60Hz" position). For 50 Hz motor 
operation, be sure Jumper J4 is set to the "1X" position and set Jumper J5 to the "50Hz" position. See Section 10.4 on page 15. 
 

1.7 

– JUMPER SETTINGS 

All jumpers have been factory set for most applications. However, some jumpers may need to be set in order to tailor the drive for a specific 
application. See Section 10 on page 15 and Section 14.3 on page 20. 
 

IMPORTANT:

 To ensure that the motor is properly protected with the I

2

t Overload Protection feature, it is required that Jumper J2 is set to the 

corresponding position for the motor horsepower being used, as shown in Figure 14 on page 15. 
 

1.8 

– TRIMPOT ADJUSTMENTS 

All trimpots have been factory set for most applications. Some applications require adjustment of the trimpots to tailor the drive for a specific 
requirement. See Section 12 on page 17 

and Section 14.2 on page 20. 

 

1.9 

– DIAGNOSTIC LEDs 

After power has been applied, observe the LEDs to verify proper drive operation, as described in Section 13 on page 18. 
 

1.10 

– SIGNAL ISOLATOR 

Provides an isolated interface between non-isolated signal sources and the drive. See Section 14 on page 18. 
 
 
 

FIGURE 1 

GENERAL CONNECTION DIAGRAM 

 

Содержание ACME SYNC ASD Series

Страница 1: ...TE The drive is factory set for 60 Hz motors For 50 Hz motors see Section 10 4 on page 15 See Safety Warnings on page 5 LISTED IND CONT EQ 70ZA 3 RoHS This Manual Covers Models ASD 24D 27D 29 29 1P 45...

Страница 2: ...Hz Motor Operation 15 10 4 2 Setting the Drive for Two Times the Rated Motor RPM 15 10 5 Boost Mode Selection J6 16 10 6 Braking Mode Selection J7 16 10 7 Run Fault Output Relay Operation Selection J...

Страница 3: ...oost Mode Selection J6 16 19 Braking Mode Selection J7 16 20 Run Fault Output Relay Operation Selection J8 16 21 Stop Contact Type Selection J9 16 22 Torque Mode Selection J10 16 23 Switching Frequenc...

Страница 4: ...lt AC Line input and 2 HP maximum with 208 230 Volt AC Line input ASD 29 Designed to accept 1 phase Terminals L1 L2 or 3 phase Terminals L1 L2 L3 AC Line input Rated for 208 230 Volt AC Line input onl...

Страница 5: ...tilated 3 phase AC induction motors will overheat if used beyond a limited speed range at full torque Therefore it is necessary to reduce motor load as speed is decreased Note Some fan cooled motors c...

Страница 6: ...rial Duty Die Cast Aluminum Case with Hinged Cover Available in dark gray finish or FDA approved white finish Simple to Operate Does not require programming Uses trimpots and jumpers which are factory...

Страница 7: ...put Voltage Operating Range Volts AC 208 15 230 15 400 460 Volt AC Line Input Voltage Operating Range Volts AC 380 15 460 15 Maximum Load Current Overload for 2 Minutes 150 Switching Frequency kHz Jum...

Страница 8: ...on See Section 10 2 on page 15 5 Jumper J5 Motor Frequency selection See Section 10 4 on page 19 6 Jumper J12 Switching Frequency and GFCI selection See Section 10 11 on page 16 7 Jumper J6 Adjustable...

Страница 9: ...ee Section 10 5 on page 16 5 Jumper J4 Frequency Multiplier selection See Section 10 4 on page 15 6 Jumper J7 Regeneration or DC Injection Braking See Section 10 6 on page 16 7 Jumper J5 Motor Frequen...

Страница 10: ...15 4 Jumper J6 Adjustable Boost selection See Section 10 5 on page 16 5 Jumper J4 Frequency Multiplier selection See Section 10 4 on page 15 6 Jumper J7 Regeneration or DC Injection Braking See Sectio...

Страница 11: ...should be taken to avoid extreme hazardous locations where physical damage can occur When mounting the drive in an enclosure the enclosure should be large enough to allow for proper heat dissipation s...

Страница 12: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 12 FIGURE 8 ASD 27D 29 29 1P 45 48 MECHANICAL SPECIFICATIONS Inches mm Tighten these screws in the sequence shown to 12 in lbs 14 kg cm...

Страница 13: ...gasket is slightly compressed The recommended tightening torque is 12 in lbs 14 kg cm do not overtighten See Figures 7 and 8 on pages 11 and 12 for the tightening sequence Application Note To avoid e...

Страница 14: ...G All equipment AC Line inputs must be disconnected from the AC power Connect all equipment AC power input lines together and connect them to the H V lead of the hi pot tester Connect the RETURN lead...

Страница 15: ...ut 10 3 AUTOMATIC RIDE THROUGH OR MANUAL START SELECTION J3 Jumper J3 is factory set to the A or AUTO position for Automatic Ride Through If the power is interrupted for up to 2 seconds the drive will...

Страница 16: ...ing Frequency 8 kHz Switching Frequency Factory setting 11 DRIVE OPERATION 11 1 START UP PROCEDURE After the drive has been properly setup jumpers and trimpots set to the desired positions and wiring...

Страница 17: ...generation Protection It is recommended that for very high inertial loads that both the ACCEL and DECEL Trimpots be set to greater than 10 seconds 12 5 DC INJECTION BRAKE TRIMPOT DECEL The drive is fa...

Страница 18: ...which provides indication of a fault or abnormal condition The information provided can be used to diagnose an installation problem such as incorrect input voltage overload condition and drive output...

Страница 19: ...ge Volts DC 0 to 2 5 thru 0 to 25 0 to 5 Signal Offset Trimpot OFFSET Range of SCALE Trimpot Setting 0 40 0 Input Current Range mA DC 4 20 Forward and Reverse Input Switch Types Dry Contact or Open Co...

Страница 20: ...ve for a specific application 14 2 1 SCALE TRIMPOT SCALE The SCALE Trimpot is factory set to run the motor at full speed with a 10 Volt DC analog signal input For a higher analog signal input 25 Volt...

Страница 21: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 21 NOTES...

Страница 22: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 22 NOTES...

Страница 23: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 23 NOTES...

Страница 24: ...uding injury to any person caused by items of our manufacture or sale Some states do not allow certain exclusions or limitations found in this warranty and therefore they may not apply to you In any e...

Отзывы: