ASD SERIES INSTALLATION AND OPERATION MANUAL 

15 

 RECONDITIONIONG THE BUS CAPACITORS 

If  this  drive  has  been  in  storage  for  over  one  year  it  is  necessary  to  recondition  the  power  supply  bus  capacitors.  To  recondition  the  bus 
capacitors,  apply  the  AC  Line,  with  the  drive  in the  Stop  Mode,  for a  minimum  of  one  hour.  Not following  this  procedure  will  cause  the  bus 
capacitors to fail. 
 
 
 

10 

 SETTING SELECTABLE JUMPERS 

The drive has customer selectable jumpers which must be set before the drive can be used. 
 

 

WARNING!

 

HIGH VOLTAGE

! Disconnect the AC Line before changing position of jumpers. 

 

10.1 

– AC LINE INPUT VOLTAGE SELECTION (ASD-24D, 27D ONLY) (J1) 

Jumper J1 is factory installed on Terminal "230V" for 208/230 Volt AC Line input. 
For  115  Volt  AC  Line  input,  the  jumper  must  be  removed  and  installed  on 
Terminal "115V". To remove the terminal, use pliers to gently rock the terminal 
back and forth while pulling it upward. See Figure 13. 
 

 

CAUTION!

 The rated AC Line voltage of the drive must match the actual 

AC Line input voltage. On ASD-24D, 27D the setting of Jumper J1 must match 
the actual AC Line input voltage. 
 
 

10.2 

– MOTOR HORSEPOWER SELECTION (J2) 

Jumper J2 must be set to the corresponding position for the motor being used. See Figure 14. 
 

FIGURE 14 

MOTOR HORSEPOWER SELECTION (J2)

 

 

ASD-24D 

ASD-27D 

   

ASD-29* 

ASD-29 (1P)* 

ASD-45* 

ASD-48* 

 

   2

**

 

 

    3

***

 

3/4 

   

1½** 

 

    

2*** 

1/2 

 

1½ 

1½ 

1½ 

1/4 

3/4 

 

1½ 

1/8 

1/2 

 

3/4 

3/4 

3/4 

The  factory  setting  is  shown  in  bold.  *J2  on  ASD-29,  29  (1P),  45,  48  is  labeled  "A,  B,  C,  D,  E".  **ASD-27D:  Rated  1½  HP  maximum  with            
115 Volt AC Line input and 2 HP maximum with 208/230 Volt AC Line input. 
***ASD-29: Rated 2 HP maximum with 1-phase AC Line input and 
3 HP maximum with 3-phase AC Line input. 

 
 

10.3 

– AUTOMATIC RIDE-THROUGH OR MANUAL START SELECTION (J3) 

Jumper J3 is factory set to the "A" or "AUTO" position for Automatic Ride-Through. If the power is 
interrupted for up to 2 seconds, the drive will shut down and then "ride-through" and automatically 
return to the set frequency. See Figure 15. 
 
If Jumper J3 is set to the "M" or "MAN" position, the drive will have to be manually restarted for a 
momentary power loss. Also see Section 13.2 on page 18 for the Status (ST) LED indication. 
 
 

10.4 

– MOTOR FREQUENCY SELECTION (J4 AND J5) 

Both Jumpers J4 and J5 must be set for the appropriate motor nameplate frequency rating. See 
Figures 16 and 17. 
 
 

10.4.1 

– SETTING THE DRIVE FOR 60 Hz OR 50 Hz MOTOR OPERATION 

The  drive  is  factory  set  to  operate  60  Hz motors. Jumper J4 is factory  set to the  "1X" 
position  and  Jumper  J5  is  factory  set  to  the  "60Hz"  position.  For  50  Hz  motors,  set 
Jumper J5 to the "50Hz" position and set Jumper J4 to the "1X" position. See Figure 16. 
 
 

10.4.2 

– SETTING THE DRIVE FOR TWO TIMES THE RATED MOTOR RPM 

The drive can also operate the motor up to two times the rated RPM. However, constant 
horsepower will result when 

operating the drive in the “2X” mode above the motor rated 

frequency. For 120 Hz output with 60 Hz motor, set Jumper J4 to the "2X" position and 
be sure Jumper J5 is set to the "60Hz" position. For 100 Hz output with 50 Hz motor, set 
Jumper J4 to the "2X" position and set Jumper J5 to the "50Hz" position. See Figure 17. 
 

 
 
 
 
 

FIGURE 13 

AC LINE INPUT VOLTAGE SELECTION 

(ASD-24D*, 27D ONLY) 

208/230 Volt AC line Input 

 (Factory Setting) 

115 Volt AC Line Input 

 

 

*Layout of ASD-24D varies slightly.

 

FIGURE 15 

AUTOMATIC RIDE-THROUGH 

OR MANUAL START SELECTION 

Automatic Ride-Through 

 (Factory Setting) 

Manual Start 

 

 

FIGURE 16 

AVAILABLE TORQUE VS. OUTPUT FREQUENCY 

 

FIGURE 17 

MOTOR FREQUENCY SELECTION

 

60 Hz 

Motor Operation 

(Factory Setting) 

50 Hz 

Motor Operation 

120 Hz 

Motor Operation 

100 Hz 

Motor Operation 

 

 

 

 

 

 

 

 

Содержание ACME SYNC ASD Series

Страница 1: ...TE The drive is factory set for 60 Hz motors For 50 Hz motors see Section 10 4 on page 15 See Safety Warnings on page 5 LISTED IND CONT EQ 70ZA 3 RoHS This Manual Covers Models ASD 24D 27D 29 29 1P 45...

Страница 2: ...Hz Motor Operation 15 10 4 2 Setting the Drive for Two Times the Rated Motor RPM 15 10 5 Boost Mode Selection J6 16 10 6 Braking Mode Selection J7 16 10 7 Run Fault Output Relay Operation Selection J...

Страница 3: ...oost Mode Selection J6 16 19 Braking Mode Selection J7 16 20 Run Fault Output Relay Operation Selection J8 16 21 Stop Contact Type Selection J9 16 22 Torque Mode Selection J10 16 23 Switching Frequenc...

Страница 4: ...lt AC Line input and 2 HP maximum with 208 230 Volt AC Line input ASD 29 Designed to accept 1 phase Terminals L1 L2 or 3 phase Terminals L1 L2 L3 AC Line input Rated for 208 230 Volt AC Line input onl...

Страница 5: ...tilated 3 phase AC induction motors will overheat if used beyond a limited speed range at full torque Therefore it is necessary to reduce motor load as speed is decreased Note Some fan cooled motors c...

Страница 6: ...rial Duty Die Cast Aluminum Case with Hinged Cover Available in dark gray finish or FDA approved white finish Simple to Operate Does not require programming Uses trimpots and jumpers which are factory...

Страница 7: ...put Voltage Operating Range Volts AC 208 15 230 15 400 460 Volt AC Line Input Voltage Operating Range Volts AC 380 15 460 15 Maximum Load Current Overload for 2 Minutes 150 Switching Frequency kHz Jum...

Страница 8: ...on See Section 10 2 on page 15 5 Jumper J5 Motor Frequency selection See Section 10 4 on page 19 6 Jumper J12 Switching Frequency and GFCI selection See Section 10 11 on page 16 7 Jumper J6 Adjustable...

Страница 9: ...ee Section 10 5 on page 16 5 Jumper J4 Frequency Multiplier selection See Section 10 4 on page 15 6 Jumper J7 Regeneration or DC Injection Braking See Section 10 6 on page 16 7 Jumper J5 Motor Frequen...

Страница 10: ...15 4 Jumper J6 Adjustable Boost selection See Section 10 5 on page 16 5 Jumper J4 Frequency Multiplier selection See Section 10 4 on page 15 6 Jumper J7 Regeneration or DC Injection Braking See Sectio...

Страница 11: ...should be taken to avoid extreme hazardous locations where physical damage can occur When mounting the drive in an enclosure the enclosure should be large enough to allow for proper heat dissipation s...

Страница 12: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 12 FIGURE 8 ASD 27D 29 29 1P 45 48 MECHANICAL SPECIFICATIONS Inches mm Tighten these screws in the sequence shown to 12 in lbs 14 kg cm...

Страница 13: ...gasket is slightly compressed The recommended tightening torque is 12 in lbs 14 kg cm do not overtighten See Figures 7 and 8 on pages 11 and 12 for the tightening sequence Application Note To avoid e...

Страница 14: ...G All equipment AC Line inputs must be disconnected from the AC power Connect all equipment AC power input lines together and connect them to the H V lead of the hi pot tester Connect the RETURN lead...

Страница 15: ...ut 10 3 AUTOMATIC RIDE THROUGH OR MANUAL START SELECTION J3 Jumper J3 is factory set to the A or AUTO position for Automatic Ride Through If the power is interrupted for up to 2 seconds the drive will...

Страница 16: ...ing Frequency 8 kHz Switching Frequency Factory setting 11 DRIVE OPERATION 11 1 START UP PROCEDURE After the drive has been properly setup jumpers and trimpots set to the desired positions and wiring...

Страница 17: ...generation Protection It is recommended that for very high inertial loads that both the ACCEL and DECEL Trimpots be set to greater than 10 seconds 12 5 DC INJECTION BRAKE TRIMPOT DECEL The drive is fa...

Страница 18: ...which provides indication of a fault or abnormal condition The information provided can be used to diagnose an installation problem such as incorrect input voltage overload condition and drive output...

Страница 19: ...ge Volts DC 0 to 2 5 thru 0 to 25 0 to 5 Signal Offset Trimpot OFFSET Range of SCALE Trimpot Setting 0 40 0 Input Current Range mA DC 4 20 Forward and Reverse Input Switch Types Dry Contact or Open Co...

Страница 20: ...ve for a specific application 14 2 1 SCALE TRIMPOT SCALE The SCALE Trimpot is factory set to run the motor at full speed with a 10 Volt DC analog signal input For a higher analog signal input 25 Volt...

Страница 21: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 21 NOTES...

Страница 22: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 22 NOTES...

Страница 23: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 23 NOTES...

Страница 24: ...uding injury to any person caused by items of our manufacture or sale Some states do not allow certain exclusions or limitations found in this warranty and therefore they may not apply to you In any e...

Отзывы: