background image

ASD SERIES INSTALLATION AND OPERATION MANUAL 

17 

12 

 TRIMPOT ADJUSTMENTS 

The drive contains trimpots which are factory set for most applications. See Figures 4 

– 6 on pages 8 – 10 for the 

location  of  the  trimpots  and  their  approximate  factory  calibrated  positions.  Some  applications  may  require 
readjustment of the trimpots in order to tailor the drive for a specific requirement. The trimpots may be readjusted as 
described in this section. 
 

 

WARNING!

 If possible, do not adjust trimpots with the main power applied. If adjustments are made with the 

main  power  applied,  an  insulated  adjustment  tool  must  be  used  and  safety  glasses  must  be  worn.  High  voltage 
exists in this drive. Fire and/or electrocution can result if caution is not exercised. The Safety Warnings on page 5 
must be read and understood before proceeding. 

 
12.1 

– MINIMUM SPEED TRIMPOT (MIN) 

Sets  the  minimum  speed  of  the  motor.  The  MIN  Trimpot  is  factory  set  to  0%  of  frequency  setting.  For  a  higher 
minimum speed setting, rotate the MIN Trimpot clockwise. See Figure 24. 

 
 
12.2 

– MAXIMUM SPEED TRIMPOT (MAX) 

Sets the maximum speed of the motor. The MAX Trimpot is factory set to 100% of  frequency setting. For a lower 
maximum speed setting, rotate the MAX Trimpot counterclockwise. For a higher maximum speed setting, rotate the 
MAX Trimpot clockwise. See Figure 25. 
 

 
12.3 

– ACCELERATION TRIMPOT (ACCEL) 

Sets the amount of time for the motor to accelerate from zero speed to full speed. The ACCEL Trimpot is factory set 
to  1.5  seconds.  For  longer  acceleration  time,  rotate  the  ACCEL  Trimpot  clockwise.  For  more  rapid  acceleration, 
rotate the ACCEL Trimpot counterclockwise. See Figure 26. 
 

Note:

 Rapid acceleration settings may cause the current limit circuit to activate, which will extend the acceleration 

time. 

 
 
12.4 

– DECELERATION TRIMPOT (DECEL) 

Sets the amount of time for the motor to decelerate from full speed to zero speed. The DECEL Trimpot is factory set 
to  1.5  seconds.  For  longer  deceleration  time,  rotate  the  DECEL  Trimpot  clockwise.  For  more  rapid  deceleration, 
rotate the DECEL Trimpot counterclockwise. See Figure 27. 
 

Application Note:

 On applications with high inertial loads, the deceleration time may automatically increase. This 

will slow down the decrease speed to prevent the bus voltage from rising

 

to the Overvoltage Trip point. This function 

is  called  Regeneration  Protection.  It  is  recommended  that  for  very  high  inertial  loads  that  both  the  ACCEL  and 
DECEL Trimpots be set to greater than 10 seconds. 

 
 
12.5 

– DC INJECTION BRAKE TRIMPOT (DECEL) 

The drive is factory set for Regenerative Braking (Jumper J7 set to the "RG" position). When the drive is set for DC 
Injection Brake (Jumper J7 set to the "INJ" position), the DECEL Trimpot is used to set the amount of time the DC 
current is applied to the motor. See Figure 28. Also see Section 10.6 on page 16. 

 
 
12.6 

– SLIP COMPENSATION TRIMPOT (COMP) 

Sets the amount of Volts/Hz to maintain set motor speed under varying loads. The COMP Trimpot is factory set to 
1.5 Volts/Hz, which provides excellent speed regulation for most motors. To increase the slip compensation, rotate 
the COMP Trimpot clockwise. To decrease the slip compensation, rotate the COMP Trimpot counterclockwise. See 
Figure 29. 
 

The slip compensation may be adjusted as follows: 
1.

  Wire an AC RMS ammeter in series with one motor phase. 

2.

  Run the motor and set the unloaded speed to approximately 50% (900 RPM on 4-pole 1500/1725 RPM motors). 

3.

  Using a tachometer, record the unloaded speed. 

4

.  Load the motor to the nameplate rated current (AC Amps). 

5.

  Adjust the COMP Trimpot until the loaded RPM is equal to the unloaded RPM. 

6.

  The motor is now compensated to provide constant speed under varying loads. 

 
 

12.7 

– MOTOR OVERLOAD (I

2

t) WITH RMS CURRENT LIMIT TRIMPOT (CL) 

UL approved as an electronic overload protector for motors. Sets the current limit (overload), 
which limits the maximum current to the motor, which prevents motor burnout and eliminates 
nuisance trips. The CL Trimpot is factory set to 160% of the drive rated current. To increase the 
current  limit,  rotate  the  CL  Trimpot  clockwise.  To  decrease  the  Current  limit,  rotate  the  CL 
Trimpot counterclockwise. See Figure 30. Also see Figure 31 on page 18. 

 

The current limit may be adjusted as follows: 
1.

  Connect an AC RMS ammeter in series with one motor phase. 

2.

  Set the CL Trimpot fully counterclockwise. 

3.

  Adjust the speed setting to 30%. 

4.

  Lock the motor shaft and adjust the CL Trimpot to 160% of the motor rated current. 

 

Note: This adjustment must be made within 6 seconds or an I

2

t Trip will occur. 

FIGURE 24 

MINIMIM SPEED 

TRIMPOT RANGE

 

 

 

FIGURE 25 

MAXIMUM SPEED 

TRIMPOT RANGE

 

 

 

FIGURE 26 

ACCELERATION 

TRIMPOT RANGE

 

 

 

FIGURE 27 

DECELERATION 

TRIMPOT RANGE

 

 

 

FIGURE 28 

DC INJECTION BRAKE 

TRIMPOT RANGE

 

 

 

FIGURE 29 

SLIP COMPENSATION 

TRIMPOT RANGE

 

 

 

FIGURE 30 

CURRENT LIMIT 

TRIMPOT RANGE

 

 

FIGURE 31 

I

2

t TRIP TIME VS. MOTOR CURRENT

 

 

Содержание ACME SYNC ASD Series

Страница 1: ...TE The drive is factory set for 60 Hz motors For 50 Hz motors see Section 10 4 on page 15 See Safety Warnings on page 5 LISTED IND CONT EQ 70ZA 3 RoHS This Manual Covers Models ASD 24D 27D 29 29 1P 45...

Страница 2: ...Hz Motor Operation 15 10 4 2 Setting the Drive for Two Times the Rated Motor RPM 15 10 5 Boost Mode Selection J6 16 10 6 Braking Mode Selection J7 16 10 7 Run Fault Output Relay Operation Selection J...

Страница 3: ...oost Mode Selection J6 16 19 Braking Mode Selection J7 16 20 Run Fault Output Relay Operation Selection J8 16 21 Stop Contact Type Selection J9 16 22 Torque Mode Selection J10 16 23 Switching Frequenc...

Страница 4: ...lt AC Line input and 2 HP maximum with 208 230 Volt AC Line input ASD 29 Designed to accept 1 phase Terminals L1 L2 or 3 phase Terminals L1 L2 L3 AC Line input Rated for 208 230 Volt AC Line input onl...

Страница 5: ...tilated 3 phase AC induction motors will overheat if used beyond a limited speed range at full torque Therefore it is necessary to reduce motor load as speed is decreased Note Some fan cooled motors c...

Страница 6: ...rial Duty Die Cast Aluminum Case with Hinged Cover Available in dark gray finish or FDA approved white finish Simple to Operate Does not require programming Uses trimpots and jumpers which are factory...

Страница 7: ...put Voltage Operating Range Volts AC 208 15 230 15 400 460 Volt AC Line Input Voltage Operating Range Volts AC 380 15 460 15 Maximum Load Current Overload for 2 Minutes 150 Switching Frequency kHz Jum...

Страница 8: ...on See Section 10 2 on page 15 5 Jumper J5 Motor Frequency selection See Section 10 4 on page 19 6 Jumper J12 Switching Frequency and GFCI selection See Section 10 11 on page 16 7 Jumper J6 Adjustable...

Страница 9: ...ee Section 10 5 on page 16 5 Jumper J4 Frequency Multiplier selection See Section 10 4 on page 15 6 Jumper J7 Regeneration or DC Injection Braking See Section 10 6 on page 16 7 Jumper J5 Motor Frequen...

Страница 10: ...15 4 Jumper J6 Adjustable Boost selection See Section 10 5 on page 16 5 Jumper J4 Frequency Multiplier selection See Section 10 4 on page 15 6 Jumper J7 Regeneration or DC Injection Braking See Sectio...

Страница 11: ...should be taken to avoid extreme hazardous locations where physical damage can occur When mounting the drive in an enclosure the enclosure should be large enough to allow for proper heat dissipation s...

Страница 12: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 12 FIGURE 8 ASD 27D 29 29 1P 45 48 MECHANICAL SPECIFICATIONS Inches mm Tighten these screws in the sequence shown to 12 in lbs 14 kg cm...

Страница 13: ...gasket is slightly compressed The recommended tightening torque is 12 in lbs 14 kg cm do not overtighten See Figures 7 and 8 on pages 11 and 12 for the tightening sequence Application Note To avoid e...

Страница 14: ...G All equipment AC Line inputs must be disconnected from the AC power Connect all equipment AC power input lines together and connect them to the H V lead of the hi pot tester Connect the RETURN lead...

Страница 15: ...ut 10 3 AUTOMATIC RIDE THROUGH OR MANUAL START SELECTION J3 Jumper J3 is factory set to the A or AUTO position for Automatic Ride Through If the power is interrupted for up to 2 seconds the drive will...

Страница 16: ...ing Frequency 8 kHz Switching Frequency Factory setting 11 DRIVE OPERATION 11 1 START UP PROCEDURE After the drive has been properly setup jumpers and trimpots set to the desired positions and wiring...

Страница 17: ...generation Protection It is recommended that for very high inertial loads that both the ACCEL and DECEL Trimpots be set to greater than 10 seconds 12 5 DC INJECTION BRAKE TRIMPOT DECEL The drive is fa...

Страница 18: ...which provides indication of a fault or abnormal condition The information provided can be used to diagnose an installation problem such as incorrect input voltage overload condition and drive output...

Страница 19: ...ge Volts DC 0 to 2 5 thru 0 to 25 0 to 5 Signal Offset Trimpot OFFSET Range of SCALE Trimpot Setting 0 40 0 Input Current Range mA DC 4 20 Forward and Reverse Input Switch Types Dry Contact or Open Co...

Страница 20: ...ve for a specific application 14 2 1 SCALE TRIMPOT SCALE The SCALE Trimpot is factory set to run the motor at full speed with a 10 Volt DC analog signal input For a higher analog signal input 25 Volt...

Страница 21: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 21 NOTES...

Страница 22: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 22 NOTES...

Страница 23: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 23 NOTES...

Страница 24: ...uding injury to any person caused by items of our manufacture or sale Some states do not allow certain exclusions or limitations found in this warranty and therefore they may not apply to you In any e...

Отзывы: