ASD SERIES INSTALLATION AND OPERATION MANUAL 

16 

10.5 

– BOOST MODE SELECTION (J6) 

Jumper J6 is factory set to the "FIX" position for Fixed Boost. For Adjustable Boost using the 
BOOST  Trimpot, set  Jumper  J6  to  the  "ADJ"  position.  See Figure 18  See Section  12.8  on 
page 18 for the Boost Trimpot. 
 
 

10.6 

– BRAKING MODE SELECTION (J7) 

Jumper J7 is factory set to the "RG" position for Regenerative Braking when the drive is set 
to "STOP". For DC Injection Braking, set Jumper J7 to the "INJ" position. See Figure 19.  
 
When the Injection Brake Mode is selected, the DECEL Trimpot is used to set the amount of 
time the DC current is applied to the motor. See Section 12.5 on page 17. 
 
 

10.7 

– RUN/FAULT OUTPUT RELAY OPERATION SELECTION (J8) 

Jumper J8 is factory set to the  "R" position for "Run" operation of the Run/Fault Relay. For 
"Fault" operation of the Run/Fault Relay, set Jumper J8 to the "F" position. See Figure 20. 
 
For the Run/Fault Relay output contacts, see Section 7.4 on page 14. The Run/Fault Relay 
contact status for various drive operating conditions is shown in Table 4 on page 14. 
 
 

10.8 

– STOP CONTACT TYPE SELECTION (J9) 

Jumper  J9  is  factory set to  the  "NO"  position for  a  normally  open  stop  contact.  For  remote 
normally closed stop contact, set Jumper J9 to the "NC" position. See Figure 21. 
 
 

10.9 

– TORQUE MODE SELECTION (J10) 

Jumper  J10  is  factory set to  the  "VT"  position for Variable Torque Mode,  which  is  used  for 
HVAC and fan applications. For Constant Torque Mode, which is desirable for most machine 
applications, set Jumper J10 to the "CT" position. See Figure 22. 
 
 

10.10 

– JUMPER J11 

Factory use only. 
 
 

10.11 

– SWITCHING FREQUENCY AND GFCI SELECTION (J12) 

Jumper J12 is factory set to the "8K" position for a switching frequency at the motor of 8 kHz. 
For 12 kHz switching frequency, set Jumper J12 to the "12K" position. This jumper also allows 
the drive to be used on standard ("G1" position) or sensitive ("G2" position) GFCIs. See Figure 
23. GFCI operation may increase audible motor noise. 
 

FIGURE 23 

SWITCHING FREQUENCY 

AND GFCI SELECTION 

 

Sensitive GFCI 

Standard GFCI 

12 kHz Switching Frequency 

8 kHz Switching Frequency

*

 

*Factory setting.

 

 
 
 

11 

 DRIVE OPERATION 

11.1 

– START-UP PROCEDURE 

After the drive has been properly setup (jumpers and trimpots set to the desired positions) and wiring completed, the start-up procedure can 
begin. If the AC power has been properly brought to the drive, the power (PWR) LED will illuminate green. The status (ST) LED will indicate 
drive status, as described in Section 13.2 on page 18. When the drive is started, the motor will begin to accelerate to the set speed. 
 

 

WARNING!

 Using a jumper to eliminate the start/stop function will cause the motor to run at the Main Speed Potentiometer setting when 

the AC Line is applied. 
 

Note: If the motor rotates in the incorrect direction, it will be necessary to disconnect the AC Line, reverse any two motor leads, and repeat the 
start-up procedure. 

 

11.2 

– RESTARTING THE DRIVE AFTER A FAULT HAS CLEARED

1,2

 

The drive monitors five faults: Undervoltage, Overvoltage, Short Circuit at the motor (phase-to-phase), Overload and Phase Loss Detection. See 
Section  13.2  on  page  18  for  the  Status  (ST)  LED  indication.  See  Section  10.3  on  page  15  for  Automatic  Ride-Through  or  Manual  Restart 
selection with Jumper J3. The drive can be restarted (after the fault has been cleared) by disconnecting the AC power, and all LEDs are no 
longer illuminated, and then reconnecting the AC power. 
 

Notes:  1.  For  an  Overload  Fault,  be  sure  the  fault  has  been  cleared  before  restarting  the  drive.  Check  the  motor  current  with  an  AC  RMS 
responding ammeter. Also, the CL setting may be set too low. See Section 12.7 on page 17. 2. For an Overvoltage Fault, if the drive is set for 
Automatic Ride-Through, the drive will automatically restart when the AC Line voltage returns to below the specified Overvoltage Trip Point. 

FIGURE 18 

BOOST MODE SELECTION 

Fixed Boost 

(Factory Setting) 

Adjustable Boost 

 

 

 

 

FIGURE 19 

BRAKING MODE SELECTION

 

Regenerative Braking 

(Factory Setting)

 

DC Injection Braking

 

 

 

 

 

FIGURE 20 

RUN/FAULT OUTPUT RELAY 

OPERATION SELECTION

 

"Run" Operation 
(Factory Setting)

 

"Fault" Operation

 

 

 

 

FIGURE 21 

STOP CONTACT TYPE SELECTION

 

Normally Open 

Stop Contact 

(Factory Setting)

 

Normally Closed 

Stop Contact

 

 

 

 

FIGURE 22 

TORQUE MODE SELECTION

 

Variable Torque Mode 

(Factory Setting)

 

Constant Torque 

Mode

 

 

 

Содержание ACME SYNC ASD Series

Страница 1: ...TE The drive is factory set for 60 Hz motors For 50 Hz motors see Section 10 4 on page 15 See Safety Warnings on page 5 LISTED IND CONT EQ 70ZA 3 RoHS This Manual Covers Models ASD 24D 27D 29 29 1P 45...

Страница 2: ...Hz Motor Operation 15 10 4 2 Setting the Drive for Two Times the Rated Motor RPM 15 10 5 Boost Mode Selection J6 16 10 6 Braking Mode Selection J7 16 10 7 Run Fault Output Relay Operation Selection J...

Страница 3: ...oost Mode Selection J6 16 19 Braking Mode Selection J7 16 20 Run Fault Output Relay Operation Selection J8 16 21 Stop Contact Type Selection J9 16 22 Torque Mode Selection J10 16 23 Switching Frequenc...

Страница 4: ...lt AC Line input and 2 HP maximum with 208 230 Volt AC Line input ASD 29 Designed to accept 1 phase Terminals L1 L2 or 3 phase Terminals L1 L2 L3 AC Line input Rated for 208 230 Volt AC Line input onl...

Страница 5: ...tilated 3 phase AC induction motors will overheat if used beyond a limited speed range at full torque Therefore it is necessary to reduce motor load as speed is decreased Note Some fan cooled motors c...

Страница 6: ...rial Duty Die Cast Aluminum Case with Hinged Cover Available in dark gray finish or FDA approved white finish Simple to Operate Does not require programming Uses trimpots and jumpers which are factory...

Страница 7: ...put Voltage Operating Range Volts AC 208 15 230 15 400 460 Volt AC Line Input Voltage Operating Range Volts AC 380 15 460 15 Maximum Load Current Overload for 2 Minutes 150 Switching Frequency kHz Jum...

Страница 8: ...on See Section 10 2 on page 15 5 Jumper J5 Motor Frequency selection See Section 10 4 on page 19 6 Jumper J12 Switching Frequency and GFCI selection See Section 10 11 on page 16 7 Jumper J6 Adjustable...

Страница 9: ...ee Section 10 5 on page 16 5 Jumper J4 Frequency Multiplier selection See Section 10 4 on page 15 6 Jumper J7 Regeneration or DC Injection Braking See Section 10 6 on page 16 7 Jumper J5 Motor Frequen...

Страница 10: ...15 4 Jumper J6 Adjustable Boost selection See Section 10 5 on page 16 5 Jumper J4 Frequency Multiplier selection See Section 10 4 on page 15 6 Jumper J7 Regeneration or DC Injection Braking See Sectio...

Страница 11: ...should be taken to avoid extreme hazardous locations where physical damage can occur When mounting the drive in an enclosure the enclosure should be large enough to allow for proper heat dissipation s...

Страница 12: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 12 FIGURE 8 ASD 27D 29 29 1P 45 48 MECHANICAL SPECIFICATIONS Inches mm Tighten these screws in the sequence shown to 12 in lbs 14 kg cm...

Страница 13: ...gasket is slightly compressed The recommended tightening torque is 12 in lbs 14 kg cm do not overtighten See Figures 7 and 8 on pages 11 and 12 for the tightening sequence Application Note To avoid e...

Страница 14: ...G All equipment AC Line inputs must be disconnected from the AC power Connect all equipment AC power input lines together and connect them to the H V lead of the hi pot tester Connect the RETURN lead...

Страница 15: ...ut 10 3 AUTOMATIC RIDE THROUGH OR MANUAL START SELECTION J3 Jumper J3 is factory set to the A or AUTO position for Automatic Ride Through If the power is interrupted for up to 2 seconds the drive will...

Страница 16: ...ing Frequency 8 kHz Switching Frequency Factory setting 11 DRIVE OPERATION 11 1 START UP PROCEDURE After the drive has been properly setup jumpers and trimpots set to the desired positions and wiring...

Страница 17: ...generation Protection It is recommended that for very high inertial loads that both the ACCEL and DECEL Trimpots be set to greater than 10 seconds 12 5 DC INJECTION BRAKE TRIMPOT DECEL The drive is fa...

Страница 18: ...which provides indication of a fault or abnormal condition The information provided can be used to diagnose an installation problem such as incorrect input voltage overload condition and drive output...

Страница 19: ...ge Volts DC 0 to 2 5 thru 0 to 25 0 to 5 Signal Offset Trimpot OFFSET Range of SCALE Trimpot Setting 0 40 0 Input Current Range mA DC 4 20 Forward and Reverse Input Switch Types Dry Contact or Open Co...

Страница 20: ...ve for a specific application 14 2 1 SCALE TRIMPOT SCALE The SCALE Trimpot is factory set to run the motor at full speed with a 10 Volt DC analog signal input For a higher analog signal input 25 Volt...

Страница 21: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 21 NOTES...

Страница 22: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 22 NOTES...

Страница 23: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 23 NOTES...

Страница 24: ...uding injury to any person caused by items of our manufacture or sale Some states do not allow certain exclusions or limitations found in this warranty and therefore they may not apply to you In any e...

Отзывы: