5.3 Application Details
1. Data Types: The data types supported by the AcuRev 1312 have
the following meanings.
Bit- binary value
Word- 16 bit unsigned integer using one register that contains 2 bytes. The data range is
0~65535.
Int16- 16 bit signed integer using one register that contains 2 bytes. The data range is
-32768~32767.
Dword- 32 bit unsigned integer using two registers that contains 4 bytes in total. The high bytes
follow the low bytes in this data type. The data range is 0-4294897295.
Int32- 32 bit signed integer using two registers that contains 4 bytes in total. The data range is
from -32768~32767.
Float-Single precision floating point number using two registers. The data range is
-2147483648~2147483647.
2.Relationship between communication value and real value.
The measurement values from the AcuRev 1312 meter obtained through Modbus may not al-
ways be equal to the real value. The values may be scaled or a relationship may need to be ap-
plied. It is very important that user is aware of these relationships when designing programs to
poll the meter, otherwise the values may not be accurate.
Parameter
Relationship
Unit
System Parameter settings and Status
The communication value equals
the real value
----
Real-time Clock, Timestamps
The communication value equals
the real value
----
Electrical measurement parameters
Electrical measurement
parameters unit
PT1 & PT2
Real = Communication/10
----
Meter run time & Load time
Real = Communication/10
Hours