www.accuenergy.com
V: 1.0 Revised: Aug. 2017
Chapter 4: Functions and Software
35
Certain settings such as clearing meter data require the permission of the user to be configured
to High.
Click on ‘Upgrade’ beside “Current Permission” and enter the password of the meter to elevate
the Permission. The Permission will stay on High for 30 minutes before being demoted back the
default Low permission status.
Note: The Permission will need to be on High so that the energy readings can be cleared and to
initialize the energy value.
For more information regarding other configurations, please refer to the AcuRev 1310 series
user manual.
4.3.5 Setting the Pulse Output:
From the “General Settings” page in the software, users can configure the meter to output puls
-
es corresponding to the energy that the AcuRev 1312 is measuring.
Under “Energy Pulse Output”, the type of energy that will be outputted needs to be selected as
either “Real Energy” or “Reactive Energy” so that when either on the energy parameter is accu-
mulating then there will be a pulse output associated for that energy parameter.
Users will need to enter the requirements for the pulse in the “Pulse Constant” and “Pulse
Width” fields.
The “Pulse Constant” is the number of pulses the user needs one pulse to represent. Enter a val-
ue from 1-60000.
Note: Please see Section 4.2 Pulse Output on how to obtain the pulse constant.
The “Pulse Width” of the pulse is the duration it will last for. Enter a value from 20-100ms.
Click “Update Device” to save the settings to the meter.
Figure 4.3.6