www.accuenergy.com
V: 1.0 Revised: Aug. 2017
AcuRev 1312
46
DIN-Rail Power Meter
Parameter
Accuracy
Resolution
Range
Active energy
0.5%
1Wh
0-999999999
Reactive energy
0.5%
1varh
0-999999999
Apparent energy
0.5%
1VAh
0-999999999
Voltage
0.5%
0.1V
10V-1000KV
Current
0.5%
0.001A
10mA-500000A
Active power
0.5%
1W
-99-99MW
Reactive power
0.5%
1var
-99-99Mvar
Apparent power
0.5%
1VA
-99-99MVA
Power factor
0.5%
0.001
-1.000-1.000
Frequency
0.2%
0.01Hz
50/60
Power demand
0.5%
1W/var/VA
99MW/Mvar/MVA
Current demand
0.5%
0.001A
10mA-5000A
Pulse Output
Isolation voltage
2500Vac
Load Voltage
0-250Vac
Load Current
100mA(max)
Power Supply
Working Power Supply
100-415Vac,50/60Hz;
100-300Vdc
Power Consumption
<2W or <10VA
Voltage
Rated Voltage
240Vac L-N/415Vac L-L
Input Impedance
2M /Phase
Measurement Frequency
50/60Hz
Accuracy
0.5%
Current Input
Stated Current (IN)
5A/1A/100mA/80mA
Start Current
10mA/2mA/0.2mA/
0.16mA
Accuracy
0.5%
Environment
Working temperature
-25 to 53° C
Storage temperature
-40 to 85° C
Relay Output
Load Voltage
250Vac30Vdc
Max Load current
5A(Resistant Load)
Isolation voltage
2000Vac(1min)
Action Time
10ms
Mechanical Life
20million times
Electrical Life
Above 50,000Times
(5A,250Vac,Resistant
Load)
Communication
RS485Baud Rate
1200-38400
Communication protocol Modbus-RTU
Infrared Communication 2000Vac(1min)
Infrared Baud Rate
10ms
SPECIFICATIONS
METERING