3. Parameter Address Table
For the complete Modbus addresses that the AcuRev 1312 supports, please reference the
AcuRev 1310 Series User Manual.
System Parameter Settings: Function Code: 03H to Read; 10H to Write
Modbus Address
Parameter
Data
Type
Prop -
erty
Range
Default #of reg-
isters
Hex
Decimal
200H
512
Meter Address
word R/W 1-247
1
1
201H
513
Baud Rate
word R/W 1200; 2400; 4800; 9600;
19200;38400
19200
1
202H
514
Parity
word R/W
0: Even parity;
1: Odd parity
2: No parity, 2 Stop Bit
3: No parity, 1 Stop Bit
3
1
203H
515
Energy Pulse Out-
put
word R/W 0: Active Power
1: Reactive Power
0
1
204H
516
Demand Mode
word R/W
0: Sliding Window;
1: Fixed Window;
2: Rolling Window
3: Thermal
0
1
205H
517
Demand Calcula-
tion Time
word R/W 1-30 minutes
15
1
206H
518
Demand Calcula-
tion Slip Time
word R/W 1-30 minutes
1
1
207H
519
Reactive Power
Calculation Method word R/W
0: True (sinusoidal);
1: Generalized (harmon-
ics present)
0
1
208H
520
VAR/PF Convention word R/W 0: IEC; 1: IEEE
0
1
210H
528
Parameter Mea-
surement side
word R/W 0: Primary side;
1:Secondary side
0
1
211H
529
Wiring Mode
word R/W
0:3LN
1:2LL
2:1LL
3:1LN
0
1
212H
530
CT2
word R/W
1:1A CT;
5:5A CT;
80:80mA CT;
100:100mA CT;
200:200mA CT;
Accord-
ing to
order
1
213H
531
CT1
word R/W 1~50000/5~50000
5
1
215H
533
PT2
word R/W 50.0~400.0
220.0
1
216H-217H
534-535 PT1
word R/W 50.0~999999.9
220.0
1
218H
536
Pulse Constant
word R/W 1-60000
5000
1