www.accuenergy.com
V: 1.0 Revised: Aug. 2017
Chapter 4: Functions and Software
27
www.accuenergy.com
27
V: 1.0 Revised: Aug. 2017
V: 1.0 Revised: Aug. 2017
www.accuenergy.com
V: 1.0 Revised: Aug. 2017
This chapter will provide users with an overview on confi guring the AcuRev 1312 to measure
data correctly and introduces the energy pulse output function of the meter. Users will also be
introduced to the AcuRev 1310 Utility software that can be used to read the meter’s data as well
as confi gure the meter.
4.1 Confi guration
The AcuRev 1312 needs to be confi gured correctly in order for it to measure the data correctly.
For the initial meter setup, The wire mode, PT and CT ratios needs to be set confi gured. Here are
the steps to setup the meter from the display. Users must ensure the lower terminal cover of
the meter has been removed to gain access to the “SET” button.
⚫ Press the “SET” key to enter the settings mode.
⚫ The password screen will be displayed. Leave the password as default “0000” if no pass-
word was confi gured. Otherwise use the “SCROLL” and ‘SET’ keys to enter the confi gured
password. “S-01 Addr” will appear.
⚫ Press the “SCROLL” key until you get to “S-08 Lt” screen. Select the required voltage wir-
ing mode. This will be based on your voltage connection. E.g. if it’s a three phase 4 wire con-
nection, select ‘3LN’.
Refer to Section 2.3 Wiring section for more details
► Press “SET” to enter edit mode.
► Press “SCROLL” to select the wiring mode.
► Press “SET” to confi rm the setting.
⚫ Press the “SCROLL” key to move to the CT2 page. This setting should already be confi g-
ured to the secondary value of the CT. After this is confi rmed, press the “SCROLL” key to
move to the next page.
⚫ The ensuing page will be “S-10” for setting the primary value of the CT. If no CT is being
used, leave this as the default value and press “SCROLL” to move to the next page. If CT’s are
being used, enter in the primary value of the CT here.
► Press “SET” to enter edit mode and to change the fl ashing digit.
► Press “SCROLL” to change the value of the digit.
► Press “SET” to confi rm the setting and move to the next page.