background image

43

3.3. Riempimento dell’impianto

Once all the system connections have been made, the heating circuit can be filled. This operation must 

be carried out with caution, respecting the following phases:

- open the radiator vent valves and make sure that the automatic valve in the boiler works;

- gradually open the filler cock (fig. 2) making sure that any automatic air vent valves installed on the system work properly;

- close the radiator vent valves as soon as water comes out;

- using the boiler pressure gauge, check that the pressure reaches a value of 1÷1.3 bar;

- close the filling cock and then vent the air again through the radiator vent valves;

- after turning on the boiler and bringing the system up to temperature, stop the pump and repeat the air venting operations;

- let the system cool down and bring the water pressure back to 1÷1.3 bar.

WARNING

The UNI CTI 8065/89 standard "Water treatment in heating systems for civil use" determines and defines the 

chemical and chemical-physical characteristics that the water used in heating systems for civil use must have, in 

particular: "... at in order to optimize their performance and safety, to preserve them over time, to ensure lasting 

regularity of operation also to the auxiliary equipment and to minimize energy consumption, thus integrating 

current laws and regulations;...".

Compliance with this rule is a legal obligation (Law 5/3/90 n.46, Presidential Decree 28/8/93 n.412).

Therefore provide for this by using specific products suitable for multimetal systems (see paragraph 3.2.4).

ATTENTION

The pressure sensor does not give electrical consent for burner start-up when the pressure is less than 0.5 bar.

The water pressure in the heating system must not be lower than 1 bar; failing that, act on the filling cock with 

which the boiler is equipped (fig. 2).

The operation must be carried out with the system cold. The digital pressure gauge allows reading the pressure in 

the heating circuit.

3.4. Starting the boiler

3.4.1. Preliminary checks

Before starting up the boiler, it is advisable to check that:

-

the smoke evacuation duct and the end part are installed in accordance with the instructions:

 

when the boiler is on, no leakage of 

combustion products from any gasket is tolerated;

- l

a boiler power supply voltage is 230 V ~ 50 Hz;

-

the system is correctly filled with water (pressure gauge 1÷1.3 bar);

-

any shut-off cocks on the system pipes are open;

-

the mains gas corresponds to the boiler calibration gas: otherwise, convert the boiler to use the available gas (see section “3.7.

Adaptation to use of other gases and burner adjustment”) : this operation must be carried out by qualified technical personnel;

-

the fuel supply cock is open;

-

there are no fuel gas leaks;

-

the main electric switch upstream of the boiler is on;

-

the 3 bar safety valve is not blocked;

-

there are no water leaks;

-

the condensate drain siphon, fitted in the boiler, drains the condensate correctly and is not blocked.

3.4.2. 

Turning on and off

To switch the boiler on and off, follow the "

User Instructions

"

.

Содержание PLAY 24

Страница 1: ...1 PLAY 24 28 32 Wall mounted gas condensing boiler for heating and DHW production PLAY 24 28 32 INSTALLATION MANUAL...

Страница 2: ...by current legislation 2 according to the provisions of Presidential Decree no 74 of 16 April 2013 the compilation of the system booklet after detecting the combustion parameters must be carried out...

Страница 3: ...to repair or direct intervention contact only qualified personnel Any repairs to the product must be carried out with the use of original spare parts Failure to comply with the above may compromise t...

Страница 4: ...d only the domestic hot water function will be enabled the system delivery temperature is displayed 5 If you want to activate both the heating function and the domestic hot water function hold down th...

Страница 5: ...ller 28 3 1 Installation rules 28 3 2 Installation 28 3 2 1 Packing 28 3 2 2 Choice of the place of installation of the boiler 28 3 2 3 Positioning of the boiler 28 3 2 4 Assembling the boiler 30 3 2...

Страница 6: ...iagram 23 fig 7 Installation template 29 fig 8 Support brackets 30 fig 9 Examples of installation 30 fig 10 Intake exhaust with coaxial ducts 35 fig 11 Dimensional dimensions for coaxial ducts 35 fig...

Страница 7: ...reasing temperature values and parameters F Key to increase temperature values and parameters To access the interface you need to press a button Activating the interface it enables access to all keys...

Страница 8: ...es parameter values and anomalies 4 Indication of the need for manual RESET of the error 5 OT connection present 6 Indication of the unit of measurement of the system pressure 7 Symbol indicating inst...

Страница 9: ...time the WINTER modes are enabled in sequence SUMMER and OFF All buttons are active in this phase With the WINTER mode active both functions are active preparation of domestic hot water and preparatio...

Страница 10: ...e the value is stored and the display returns to its normal operation Pressing the sanitary button C fig 1 displays the temperature of the heating delivery water Pressing the buttons E fig 1 or F fig...

Страница 11: ...n 1 sec n00 1 sec and the value of the relative parameter 5 sec alternate on the screen By briefly pressing the button F fig 1 it is possible to scroll through the various indices When you reach the l...

Страница 12: ...9 C 1 In5 Return probe temperature display 9 99 C 1 In6 Real SET heating temperature display Par 13 INST Par 14 INST C 1 In7 Power level display 0 100 1 In8 Flowmeter value display 0 99 l min 0 1 In9...

Страница 13: ...MER position Sanitary function active The DHW delivery temperature is displayed and the symbol flashes Boiler selector in WINTER position Sanitary function active The DHW delivery temperature is displ...

Страница 14: ...anomaly Ignition failure Intervention of the safety thermostat Parasitic flame Lack of circulation Return NTC probe failure System overtemperature TCH TSP81 Delta T CH Ret TSP82 1 Gas valve modulator...

Страница 15: ...ly at start up 2 Problem on the SGV circuit Loss of flame upon ignition for more than 6 consecutive times Software Error Card not configured Generic block Table 4 BOILER STATUS LCD display in case of...

Страница 16: ...it the error is released The anomaly signal disappears on the interface and the display turns off 1 8 Automatic elimination of system air By pressing the and keys simultaneously for the cycle time the...

Страница 17: ...nd the value that is being set for the heating water temperature is indicated When the heating system requires heat the heating symbol flashes on the display 2 fig 1 and the instantaneous temperature...

Страница 18: ...water increasing it when the outside temperature decreases and decreasing it when the outside temperature increases thus improving the environmental comfort and saving fuel The maximum temperatures o...

Страница 19: ...f the air intake and or flue gas exhaust systems the boiler is blocked the display shows the flashing code E13 0 E96 intervention of the fumes probe In this case contact an Authorized Service Center o...

Страница 20: ...rding to the settings made on the control panel ignoring the settings made on the Re motion Control In this case contact an Authorized Service Center or qualified personnel for maintenance 1 12 Mainte...

Страница 21: ...er precedence flow meter User interface Interface with built in LCD for viewing and controlling the boiler operating status OFF UNLOCK WINTER and SUMMER Heating water temperature regulator 20 80 C sta...

Страница 22: ...nlet Gas inlet Siphon inspection cap Heating system delivery C R RS RC Bottom view View from above Domestic hot water outlet Return no heating system Drain cock and safety valve drain Filling cock SI...

Страница 23: ...sensor 11 Return temperature sensor 12 3 bar safety valve 13 Pressure transducer 14 Deaerator 15 Circulator 16 Drain cock 17 Filling cock 18 Cold water flow meter 19 Secondary plate exchanger 20 Domes...

Страница 24: ...pressure of the sanitary circuit bar 6 6 6 Specific flow rate of sanitary water T 30K l min 12 13 3 14 Power supply Voltage Frequency V Hz 230 50 230 50 230 50 Power supply fuse A 3 15 3 15 3 15 Maxi...

Страница 25: ...termica in stand by Pstby 0 069 kW elmin 0 054 kW Consumo energetico del bruciatore di accensione Pign 0 kW Auxiliary electricity consumption At full load Part load In stand by mode PSB 0 004 kW Cons...

Страница 26: ...tricity consumption At full load Part load In stand by mode PSB 0 004 kW Other elements Stand by heat loss Energy consumption of the ignition burner Annual energy consumption QHE 55 GJ Emission of nit...

Страница 27: ...electricity consumption At full load Part load In stand by mode PSB 0 005 kW Other elements Stand by heat loss Energy consumption of the ignition burner Annual energy consumption QHE 62 7 GJ Emission...

Страница 28: ...boiler to the wall fig 7 3 2 2 Choice of the place of installation of the boiler When determining the place to install the boiler take the following into account the indications contained in paragrap...

Страница 29: ...PL L L LA A A AY Y Y Y S S S SV V V V M M M M R R R R 173 173 93 10 86 137 O 100 O 80 122 138 67 68 20 A SOLUTION A wall installation with bracket supplied SOLUTION B wall installation with template o...

Страница 30: ...ing return R at the same points on the template lower part prepare a connection for the condensate drain and a drain for the 3 bar safety valve hang the boiler on the hooks of the dowels connect the b...

Страница 31: ...y prohibited In the event of repeated shutdowns of the boiler it is necessary to have the air intake flue gas exhaust ducts checked which could be blocked or inadequate for the disposal of fumes into...

Страница 32: ...lding I 300 From the ground or other walking surface L 2200 Between two terminals vertically M 1500 Between two terminals horizontally N 1000 Between two terminals horizontally O 2000 Same but with op...

Страница 33: ...y case be positioned within a square with a side of 500 mm The boiler must be equipped with a fan upstream of the combustion chamber heat exchanger Type C43 Boiler designed to be connected to a collec...

Страница 34: ...the maximum length allowed must be decreased by 1 metre The wall terminal decreases the maximum permissible length by 1 5 metres The air intake part must have a downward slope of 1 in the outlet direc...

Страница 35: ...ased by 1 metre For each 45 bend added the maximum length allowed must be decreased by 0 5 metres The roof terminal decreases the maximum permissible length by 3 metres The wall terminal decreases the...

Страница 36: ...function press and hold the key B fig 1 for 3 seconds and you will return to normal operation The duration of the chimney sweep function is 15 minutes 3 2 8 Connection to the gas network The gas supp...

Страница 37: ...here Unless particular prohibitions exist the condensate produced during the combustion phase must be conveyed by means of the condensate drain to a drain system which makes it flow to the domestic w...

Страница 38: ...e used correct operation of the remote control itself and of the boiler is not guaranteed The Remote Control cables must be connected to terminals A and B of the terminal board fig 21 and fig 22 To in...

Страница 39: ...by the manufacturer If non original external probes not supplied by the manufacturer are used correct operation of the external probe and the boiler is not guaranteed The probe for measuring the exter...

Страница 40: ...ng to value 30 if the external temperature is equal to 5 C the delivery temperature will be equal to 70 C By setting a fictitious ambient temperature of 23 C again with an external temperature of 5 C...

Страница 41: ...19 Thermostat 0 Smoke probe 1 0 1 1 DO NOT MODIFY P20 DHW setpoint minimum value selection 35 50 35 P21 Selection of low temperature zones 0 1 0 0 high temperature 1 low temperature P22 Not used P23 P...

Страница 42: ...c 30 P57 Fan speed increase selection 0 10 0 DO NOT MODIFY P58 Not used P59 Not used P60 Additional offset to the switch off temperature after burner ignition 0 20 0 DO NOT MODIFY P61 Smoke outlet tem...

Страница 43: ...e 28 8 93 n 412 Therefore provide for this by using specific products suitable for multimetal systems see paragraph 3 2 4 ATTENTION The pressure sensor does not give electrical consent for burner star...

Страница 44: ...ximum value The circulator is set to constant T mode during production For correct boiler operation it is recommended not to change the factory setting If it is necessary to change the settings contac...

Страница 45: ...45 3 6 3 Wiring diagram fig 21...

Страница 46: ...ressing the or keys F or E fig 1 changes the value of the selected parameter Pressing the key D fig 1 for the cycle time stores the new setting By pressing the and keys B C fig 1 simultaneously for th...

Страница 47: ...ce and from the Remote Command on page 48 The AUTO mode is the recommended one and which allows the greatest freedom to modify the CO2 OPERATIONS TO BE CARRIED OUT Enter the chimney sweep function see...

Страница 48: ...9 3 9 7 0 1 16 kW LPG 10 4 10 6 0 1 24 kW Methane 9 3 9 8 0 1 24 kW LPG 10 4 10 7 0 1 28 kW Methane 9 0 9 0 0 1 28 kW LPG 10 5 10 5 0 1 32 kW Methane 8 4 10 6 0 1 32 kW LPG 10 5 10 6 0 1 Table 26 CO2...

Страница 49: ...increase decrease the O2 value or change the system power if the flame symbol flashes Premere per il tempo ciclo il tasto D fig 1 per attivare il menu O2 Premendo i tasti o F o E fig 1 sar possibile...

Страница 50: ...f the gas nozzles cleaning of the air intake and fume evacuation circuit cleaning of the heat exchanger cleaning the siphon and the condensate drain pipes If you are intervening on the boiler for the...

Страница 51: ...circuit problem E 91 Flame loss for more than 6 consecutive times with max ignition correction ON E 98 SW error board error E 99 Generic fault Table 28 Table of technical problems 1 This control is a...

Страница 52: ......

Страница 53: ......

Страница 54: ...and all powers meet the provisions on tax deductions for energy redevelopment costs according to law 205 2017 2018 budget law It also declares that they have an efficiency eta s greater than 90 which...

Страница 55: ...2...

Страница 56: ...itolo puramente indicativo la A2B Accorroni E G S r l si riserva di apportare eventuali modi che senza alcun preavviso web site www accorroni it e mail a2b accorroni it A2B Accorroni E G s r l Via d A...

Отзывы: