34
T
ype
C13
Play
24
The minimum permitted length of horizontal coaxial pipes is 1
meter excluding the first bend.The maximum permitted length of
100/60 mm horizontal coaxial pipes is 10 meters including the first
bend. For each added straight pipe of length equal to 1 metre, the
maximum permissible length must be decreased by 1 metre.For
each 90° bend added, the maximum length allowed must be
decreased by 1.5 metres.For each 45° bend added, the maximum
length allowed must be decreased by 1 metre.The wall terminal
decreases the maximum permissible length by 1.5 metres.The air
intake part must have a downward slope of 1% in the outlet
direction, to prevent rainwater from entering.
Play 28
The minimum permitted length of horizontal coaxial pipes is 1
meter excluding the first bend.The maximum permitted length of
100/60 mm horizontal coaxial pipes is 7 meters including the first
bend.For each added straight pipe of length equal to 1 metre, the
maximum permissible length must be decreased by 1 metreFor
each 90° bend added, the maximum length allowed must be
decreased by 1.5 metres. For each 45° bend added, the maximum
length allowed must be decreased by 1 metre.The wall terminal
decreases the maximum permissible length by 1.5 metres.The air
intake part must have a downward slope of 1% in the outlet
direction, to prevent rainwater from entering.
Play 32
The minimum permitted length of horizontal coaxial pipes is 1
meter excluding the first bend.
The maximum permitted length of 100/60 mm horizontal coaxial
pipes is 6 meters including the first bend.
For each added straight pipe of length equal to 1 metre, the
maximum permissible length must be decreased by 1 metre.
For each 90° bend added, the maximum length allowed must be
decreased by 1.5 metres.
For each 45° bend added, the maximum length allowed must be
decreased by 1 metre.
The wall terminal decreases the maximum permissible length by
1.5 metres.
The air intake part must have a downward slope of 1% in the outlet
direction, to prevent rainwater from entering.
T
ype
C33
Play 24
The minimum permissible length of vertical coaxial pipes is 1
meter.The maximum permitted length of the 100/60 mm vertical
coaxial pipes is 10 metres.For each added straight pipe of length
equal to 1 metre, the maximum permissible length must be
decreased by 1 metre. For each 90° bend added, the maximum
length allowed must be decreased by 1.5 metres.For each 45° bend
added, the maximum length allowed must be decreased by 1
metre.The roof drain decreases the maximum permissible length by
1.5 metres.
Play 28
The minimum permissible length of vertical coaxial pipes is 1
meter.The maximum permitted length of the 100/60 mm vertical
coaxial pipes is 7 metres.For each added straight pipe of length
equal to 1 metre, the maximum permissible length must be
decreased by 1 metre. For each 90° bend added, the maximum
length allowed must be decreased by 1.5 metres. For each 45°
bend added, the maximum length allowed must be decreased by 1
metre.The roof drain decreases the maximum permissible length by
1.5 metres.
Play 32
The minimum permissible length of vertical coaxial pipes is 1 meter.
The maximum permitted length of the 100/60 mm vertical coaxial
pipes is 6 metres.
For each added straight pipe of length equal to 1 metre, the
maximum permissible length must be decreased by 1 metre. For
each 90° bend added, the maximum length allowed must be
decreased by 1.5 metres.
For each 45° bend added, the maximum length allowed must be
decreased by 1 metre.
The roof drain decreases the maximum permissible length by 1.5
metres.
3.2.6.2.
Air intake/flue gas exhaust with coaxial ducts with a diameter of 100/60 mm
These values refer to air intake/fume exhaust ducts made using original rigid and smooth pipes, supplied
by the manufacturer.