6
(C) MAXIMUM PIPE LENGTH
(D) MAXIMUM DIFFERENCE IN HEIGHT (between U.E and U.I.)
(E) ADDITIONAL REFRIGERANT AMOUNT (over 5 m)
configuration the effective length of the pipes is 6 m horizontally
and 4 m vertically, in total 10 m. We will then add 100 grams of
R410a refrigerant gas or 5 m x 20 g / m = 100 grams.
Example C - D - E
of table 4
4 m
6 m
WARNING!
In fig. 5 we report an example of an inadmissible application,
with a distance of 10 meters but with a difference in height of> 5
meters.
Fig. 5
6 m
4 m
Table 4 - Admissible distances U.I. - U.E.
5*m
3*m
15*m
5*m
20*g/m
HR 3.0
5*m
3*m
15*m
5*m
20*g/m
HR 7.8
5*m
3*m
15*m
5*m
20*g/m
HR 9.0 INV
Models
Maximum length allowed
without adding refrigerant
Minimum allowed length
of refrigerant gas
Maximum length of refrigerant
gas piping
Maximum admissible height
difference between U.E and U.I.
U.I. Additional refrigerant
quantity over 5 meters
A
B
C
D
E
Failure to comply with this application will result in the
non-ignition by the authorized assistance
(A) INSTALLATION WITHIN 5 METERS
Example of installation without additional gas refill R410a
refrigerant, distance 4 meters.
2 m
0,5 m
1,5 m
Example A
table 4
(B) INSTALLATION WITH MINIMUM PERMISSIBLE LENGTH
The distance between the Indoor Unit and Outdoor Unit is less
than 3 meters (as in this case where the length of the pipes does
not exceed 2 meters), the pipes must be cut to 3 meters and
rolled up the final part in correspondence with the outdoor unit.
Spiral length 1 meter
0,5 m
1,5 m
Example B
table 4