The conditions that cause the WEST manifold pump to
activate are as follows:
S_4≥TABC+
Hysteresis value
e
S_4≥S_2+
Hysteresis value
The following are the conditions that cause the collector pump
to shut down:
S_4<TABC
or
S_4<S_2
Where is it:
S_1: Temperature detected by the collector probe (EST).
S_2: Temperature detected by the boiler probe.
S_4: Temperature detected by the collector probe (WEST).
TABC: Temperature set in installer parameter P2. ABC function
hysteresis value: 3.0 ° C (fixed not modifiable)
The only active controls will be those relating to maximum
temperatures and safety.
RESET
To reset the device, press the button indicated with 'RESET'
located under the removable door; DO NOT USE NEEDLES.
10.8
INSTALLER PARAMETERS
To access the installer parameters press
‘
8
’.
Password entry
The display will show 'PWD 0000' with the first digit on the
left flashing to indicate the password request. The keys are
used to enter the 4-digit password
‘
’
o
r
‘
’;
press key
‘
8
’
as well as confirming the digit entered
,
you will pass to the selection of the second digit and so on up to
the last.
By confirming the last digit, using the '8' key, you will access the
installer parameters.
The control unit leaves the factory with the password '0000'.
Modi
fy
Password
If you want to change the stored password, after pressing the
key
‘
8
’,
proceed as follows
:
PRE
SS KEY
‘MENU’.
PRESS
‘MENU’.
PUT THE ACTUAL
PASSWORD.
(same procedure described previously)
DISPLAY
SHOWS
‘PWDN0000’.
INS
ERT
N
EW
PASSWORD.
DISPLAY
SHOWS
‘PWDC0000’.
DISPLAY
SHOWS
‘PWDN0000’.
INSER
T
N
EW
PASSWORD.
THE CONTROL UNIT STORES THE NEW PASSWORD
AND ACCESSES THE INSTALLER PARAMETERS.
WARNING!
In "installer parameters" mode all the outputs are disabled. All
the default values indicated are to be considered indicative as
they may vary according to the version and without notice.
PRESS KEY
‘
8
’
FROM THE HOME SCREEN
.
THE DISPLAY SHOWS
‘PWD 0000’.
ENTER THE CURRENT PASSWORD.
THE FIRST 'INSTALLER
PARAMETER' IS DISPLAYED.
THROUGH THE ARROWS
‘
’ o ‘
’
IT IS
POSSIBLE TO SCROLL CYCLICALLY
BETWEEN THE INSTALLER PARAMETERS:
P1:
SYSTEM TYPE SELECTION
‘SCH’
P2:
THERMAL DATA SETTING
‘DATA’
P3:
MANAGE OF ANTI-FREEZE PARAMETERS
‘O AF’
P4:
ACOUSTIC SIGNAL MANAGEMENT
‘BEEP’
P5:
RELAY LOGIC SELECTION
‘ACT’
P6:
ACCOUNTING HOURS OF INTEGRATION
‘C AH’
P7: TEST
LOADS CONNECTED
‘TEST’
P8:
ACCOUNTING ENERGY PRODUCED
‘SEM’
P9:
RECOOLING FUNCTION
‘REF’
P10:
PERIODIC ACTIVATION OF LOADS
‘PVK’
P11:
UNIT OF MEASURE
‘UNITÀ’
P12: LIMIT TEMP. MINIMUM COLLECTOR 'MTL'
P13: SETTING OF PWM 'ERP' OUTPUTS
P14: 'SAFE' COLLECTOR RESET TEMPERATURE
P15:
VACUUM TUBES
‘VTC’
P16: ANTI-LEGIONELLA
‘LEG’
PRERSS KEY
‘
8
’
TO ENTER IN MODIFICATION OF
THE SELECTED PARAMETER.
CONFIGURE THE DATA RELATING TO EACH
SINGLE PARAMETER AS SHOWN BELOW.
PRESS THE 'esc' KEY TO RETURN TO THE
SELECTION OF INSTALLER PARAMETERS.
WAIT 20 SECONDS OR PRESS THE 'esc' KEY TO EXIT
THE INSTALLER MODE.
P1:
SYSTEM TYPE SELECTION
By pressing the keys
‘
’ o ‘
’
all feasible systems will be
shown (if for the selected system one of the probes has a
problem or is not connected, this probe will flash on the
display).
To confirm the desired system, press the key
‘
8
’
the
control unit will memorize the choice and will return to showing the
list of parameters.
To cancel the selection, press the 'esc' key, in this case the control
unit will abandon the modification made and will return to showing
the list of parameters.
The parameters that influence the adjustment of the selected
scheme are listed below and can be modified using the second
installer parameter.