| Error resolution and maintenance –
Taking the Wallbox eMH2 out of operation
30
3
Flick the pivot lever of the internal RCCB into the
0
position (connection to the electricity grid is
interrupted).
y
Also flip the pivot lever of the internal MCB
into position
0.
4
Close the access flap, hook the housing cover
onto the upper edge of the housing base and lock
it using the housing cover key.
5
Open your domestic power distribution box, dis-
connect the power supply cable from the electrici-
ty grid via the MCB and close the distribution box.
The Wallbox eMH2 is no longer connected to the electricity grid and can be removed by a qualified specialist electri-
cal contractor if required.
Always measure the voltage between the phases and the neutral conductor of the power supply cable
before you start dismantling the wallbox.