|     Error resolution and maintenance  –   

Identifying errors

24

Error resolution and maintenance

Under certain circumstances, malfunctions may occur during operation that prevent or restrict charging. The Wallbox 

eMH2 independently detects errors and indicates them in the form of cyclically repeating LED flash patterns.

Identifying errors

The following errors may occur:

Error F1

Description

Flash pattern

Per cycle, the red LED flashes once,  

followed by the green LED flashing four times.

Cause

Suggested solution

The main contactor of the wallbox does not open.

 

ƒ

Check the RCCB of the wallbox and bring its pivot lever into 

the I position if necessary.

 

ƒ

Switch the power supply for the wallbox off and then back 

on again. The error should have been reset automatically.

 

ƒ

Should the error persist, please take the wallbox out of 

operation (see page 29) and contact a qualified specialist 

electrical contractor to resolve the error.

Error F2

Description

Flash pattern

Per cycle, the red LED flashes once, followed by 

the green LED flashing three times and the blue 

LED flashing once.

Cause

Suggested solution

The firmware has detected a disallowed operat-

ing state during the initial or a periodic self-test.

 

ƒ

Switch the RCCB of the wallbox off and then back on again. 

The error should have been reset automatically.

 

ƒ

Should the error persist, please take the wallbox out of 

operation (see page 29) and contact a qualified specialist 

electrical contractor to resolve the error.

Error F3

Description

Flash pattern

Per cycle, the red LED flashes once, followed 

by the green and blue LEDs alternately flashing 

twice.

Cause

Suggested solution

The internal DC fault current module has detect-

ed a DC fault current.

 

ƒ

When this error occurs for the first time, the charging 

procedure is interrupted for 30 seconds and then restarted 

automatically. If the error occurs again immediately, the 

charging procedure is terminated permanently: A new 

charging procedure is only possible after disconnecting the 

vehicle from the wallbox.

 

ƒ

There is possibly an electrical fault in the charging system of 

the vehicle. Do not charge the vehicle, and immediately con-

tact a qualified specialist repairer. In addition, always consider 

the notices provided in the operating manual of the vehicle.

Содержание WALLBOX eMH2 EN

Страница 1: ...Article No 0301772_EN_a EN WALLBOX eMH2 Installation and Operating manual...

Страница 2: ...has carried out the installation of your wallbox and any accessories Downloads Further information and documents regarding your wallbox and accessories are available at https www toyota tech eu https...

Страница 3: ...of the wallbox 12 Data cable connections 14 Commissioning the wallbox 15 Configuring the Wallbox eMH2 17 Stand alone operation of a Master wallbox 17 Stand alone operation of a Slave wallbox 17 Charg...

Страница 4: ...be available to all users of the product Only use accessories intended and sold for the product by ABL Do not install this device in close vicinity to running water water jets or areas subject to flo...

Страница 5: ...nger provided y The product does not function properly or has been otherwise damaged User information Ensure that the rated voltage and rated current of the product comply with the parameters of your...

Страница 6: ...ruzioni ES Indicaciones de seguridad Gu a r pida NL Veiligheidsinstructies Verkorte handleiding FI Turvallisuusohjeet Pikaopas NO Sikkerhetsanvisninger Hurtigreferanse 1 Wall plugs 8 40 mm 4 pcs T20 p...

Страница 7: ...eMH2 to the pole h 365 mm b 265 mm t 3 mm LAK32B3 PZ42D00B04 Type 2 charging cable according to IEC 62196 2 up to 32 A 240 415 V AC 3 phase length ca 5 m LAK32C3 PZ42D00B05 Type 2 charging cable acco...

Страница 8: ...ience as well as their knowledge of the relevant standards is able to assess and carry out the working steps described in this manual and recognise potential hazards Installation site requirements The...

Страница 9: ...IT Avvertenze di sicurezza Brevi istruzioni ES Indicaciones de seguridad Gu a r pida NL Veiligheidsinstructies Verkorte handleiding FI Turvallisuusohjeet Pikaopas NO Sikkerhetsanvisninger Hurtigrefer...

Страница 10: ...safety rules 1 Cut power source 2 Secure all cut off devices 3 Verify absence of voltage 4 Ground and short circuit 5 Cover or bar access to adjacent components under voltage Proceed as follows 1 Cut...

Страница 11: ...to prepare the wallbox 7 Open the housing cover of the wallbox with the housing cover key and put it aside 8 Loosen the screw of the internal electronic com ponents cover using the screwdriver Torx an...

Страница 12: ...nhead screws you inserted at the installation site in Step 6 12 Fix the housing base to the mounting surface by inserting the two remaining panhead screws into the two lower fixing points using the sc...

Страница 13: ...Marks for Phase 1 current carrying conductor Brown 5 L1 Phase 2 current carrying conductor Black 3 L2 Phase 3 current carrying conductor Gray 1 L3 Neutral Blue N Protective earth Green Yellow PE Conne...

Страница 14: ...to the housing base in Step 10 of Sec tion Electrical connection of the wallbox y Cut the data cables to the required length with the pliers if necessary 2 Connect the twisted wire strands of the firs...

Страница 15: ...ting resistors 120 Ohm A M B CONTROL A M B METER A M B CONTROL A M B METER Commissioning the wallbox To commission the wallbox the power supply cable must be connected to the electricity grid The foll...

Страница 16: ...g current and tripping time Rotating field testing as well as additional tests according to local regulations 3 Replace the electronic components cover onto the housing base and fix it into place with...

Страница 17: ...oviders You can obtain further information from the dealer where your purchased your wallbox Stand alone operation of a Slave wallbox In principle Slave wallboxes are factory preconfigured to operate...

Страница 18: ...spring terminals for the CONTROL bus of the wallbox The CONTROL bus is always assigned to the left three spring terminals of each terminal block Using the USB RS485 cable connect the USB RS485 adapte...

Страница 19: ...s are now retrieved and displayed in the Controller settings window 11 From the Controller settings Address drop down list select value 1 12 Click the Device specification Write button to transfer the...

Страница 20: ...wallbox y The Devices field now shows the device RFIDM60 standalone CONFIG MODE 22 Close the Configuration Software application using the X button in the top right corner of the application window an...

Страница 21: ...se and fix it into place with the screw you removed in Step 3 25 Hook the housing cover onto the upper edge of the housing base and lock it using the housing cover key The wallbox must now be disconne...

Страница 22: ...s 3 Prepare the charging cable of the wallbox y Fixed cable variant Type 2 Slightly lift up the charging connector and pull it from its compartment y Socket variant Type 2 Open the charging socket fla...

Страница 23: ...lowing a request by the vehicle the blue LED is ON y When the charging procedure is paused or completed the blue LED pulsates The charging procedure may be paused by the vehicle Otherwise the charging...

Страница 24: ...ng three times and the blue LED flashing once Cause Suggested solution The firmware has detected a disallowed operat ing state during the initial or a periodic self test Switch the RCCB of the wallbox...

Страница 25: ...e plug could not be locked inside the charging socket of the wallbox The wallbox automatically reinitiates the self test after 30 seconds after two failed self tests the charging procedure is terminat...

Страница 26: ...s exceeding the preset maximum current The wallbox automatically reinitiates the charging proce dure every 60 seconds If the error persists the wallbox and or the vehicle must be checked please contac...

Страница 27: ...error please check the electrical connection and parameters for the wallbox and set the charging current to a value above 20 A If the error cannot be resolved please contact the specialist electrical...

Страница 28: ...ehicle is not recognized Cause and suggested solution The charging cable is not properly plugged in y Fixed cable variant remove the charging connector from the vehicle s charging inlet and plug it ba...

Страница 29: ...onto the upper edge of the housing base and lock it using the housing cover key Should the RCCB malfunction during testing you must not continue to operate the wallbox under any circumstances Contact...

Страница 30: ...the upper edge of the housing base and lock it using the housing cover key 5 Open your domestic power distribution box dis connect the power supply cable from the electrici ty grid via the MCB and cl...

Страница 31: ...e 30 C to 40 C Storage temperature 30 C to 85 C Relative humidity 5 to 95 no condensation Class of protection I Degree of protection housing IP44 IP54 plugged unplugged Overvoltage category III Impact...

Страница 32: ...014 30 EU EMC Directive 2011 65 EU RoHS Guideline 2012 19 EU WEEE Directive 2014 35 EU Low voltage directive Standards governing electromagnetic interference EMV IEC 61851 21 2 Conductive charging sys...

Страница 33: ...ection between two wallboxes A 2Y L 2Y ST III BD 4 2 0 8 mm Cat5 UTP Cat6 UTP LiYCY TP 4 2 0 75 mm Please note that these are recommendations only the conductor cross section must be adjusted accord i...

Страница 34: ...esidual Current Circuit Breaker LED Light Emitting Diode RCM Residual Current Monitor RFID Radio Frequency Identification T button Testing button Copyright and disclaimer Copyright 2020 Version 030177...

Страница 35: ...Service 35...

Страница 36: ...ABL SURSUM Bayerische Elektrozubeh r GmbH Co KG Albert B ttner Stra e 11 D 91207 Lauf Pegnitz https www toyota tech eu https www lexus tech eu MADE IN GERMANY...

Отзывы: