53
O PER AT I O N , M A I N T EN A N C E , A N D I N S TA L L AT I O N G U I D E
1
LC
D
Parameters
(continued)
*Default
Device Parameters (continued)
Hight current alarm
Status
Enabled
If measured current is higher than ten times the
nominal value device will prevent all operations
and show high current alarm on-screen. After
high current status is over, device will start
operating normally.
Disabled*
Alarm reset required
Yes
User confirmation is required before re-entering
normal operation after high current status.
No*
Normal operation is started automatically after
high current status.
Transfer to Dead Source
On*
User can transfer to an unavailable source by
using HMI keys I/II or by a remote command.
Off
Transfer to an unavailable source is disabled.
Source Loss Center-Off Delay
On*
User can select whether to always run the
'center-off' timer or skip it if there is no voltage
on any of the phases on the source from where
the ATS is transferring from.
Off
Source Loss Pre-Signal Delay
On*
User can select whether to always run the pre-
signal delays 'elevator pre-signal S1-S2', 'elevator
pre-signal S2-S1', 'pre-transfer S1 to S2', 'pre-
transfer S2 to S1' timers or skip these if there is
no voltage on any of the phases on the source
from where the ATS is transferring from.
Off
Содержание Zenith ZTG T Series
Страница 2: ...2 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 6: ...6 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 10: ...10 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 38: ...38 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 60: ...60 ZENITH ZTG D CT T SERIES 1600 3000 A 1 LCD ...
Страница 104: ...104 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 116: ...2 116 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 120: ...2 120 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 123: ...123 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...