70
1
Z E N ITH Z TG ( D/C T ) T-S E R I E S 16 0 0 -3 0 0 0 A
—
5.5 Using Ekip Com _ -modules
Suitable Ekip Com_ -modules are:
• Ekip Com Modbus RTU
• Ekip Com Profibus DP
• Ekip Com DeviceNet
• Ekip Com Modbus TCP
• Ekip Com Profinet
• Ekip Com EtherNet/IP
5.5.1 Ekip Com Modbus RTU -module
The Ekip Com Modbus RTU is a communi-
cation accessory module, that integrates
the automatic transfer switch in an indus-
trial remote supervision and control net-
work. The module is suitable for all ZTG
(D/CT) 1600-3000 A, 208-480 Vac auto-
matic transfer switches.
It can be connected to a RS-485 network
with a Modbus RTU communication pro-
tocol, and allows you to:
• Connect the automatic transfer switch
to the network, with dialog functional-
ity.
• Provide the status information of the
automatic transfer switch (e.g. open,
closed).
For the communication lines W1 (A) and
W2 (B), Belden type 3105 A or equivalent
cables must be used.
—
Fig. 5.10 Ekip Com Modbus RTU -module