47
O PER AT I O N , M A I N T EN A N C E , A N D I N S TA L L AT I O N G U I D E
1
LC
D
Operation
*Default
Bypass Time Delay
Bypass any currently running time delay.
HMI Control Keys
1)
Enabled*
Disabled
Energy Counters
Reset
Operation mode
AUTO*
Automatic switch control mode.
2)
MAN momentary
Manual operation mode but warning that
device is in manual mode will be shown by
HMI. ATS will automatically send and
remove the generator start signal but user
intervention is required to initiate transfer
and retransfer.
MAN permanent
Manual operation mode but warning that
device is in manual mode will be shown by
HMI. ATS will automatically send and
remove the generator start signal but user
intervention is required to initiate transfer
and retransfer.
MAN retransfer
Same as AUTO but automatic retransfer
sequence is disabled. Load will be kept on
non-priority source until operator manually
(by HMI or manual handle) or remotely
operates the load back to priority source.
1)
Note: Disables also 0-key in OXB models!
2)
Note: When automatic mode parameter is confirmed there is 3 second delay before entering it.
Содержание Zenith ZTG T Series
Страница 2: ...2 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 6: ...6 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 10: ...10 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 38: ...38 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 60: ...60 ZENITH ZTG D CT T SERIES 1600 3000 A 1 LCD ...
Страница 104: ...104 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 116: ...2 116 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 120: ...2 120 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 123: ...123 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...