Settings
*Default
Standard I/O Settings (continued)
O 01
Function
No Function
Output disabled.
Alarm / Product
availability*
Signals any active alarms or ATS being disabled for
automatic transfer operations.
Load Connected to S1
Switch in position I.
Load Disconnected
Switch in position O.
Load Connected to S2
Switch in position II.
Pre-transfer Signal 1
Signal is activated and transfer is delayed according
to pre-transfer delay. Signal is kept activated
according to post-transfer delay after transfer.
Pre-transfer Signal 2
Signal is activated and transfer is delayed according
to pre-transfer delay. Signal is kept activated
according to post-transfer delay after transfer.
Pre-transfer Signal 3
Signal is activated and transfer is delayed according
to pre-transfer delay. Signal is kept activated
according to post-transfer delay after transfer.
Pre-transfer Signal 4
Signal is activated and transfer is delayed according
to pre-transfer delay. Signal is kept activated
according to post-transfer delay after transfer.
Source 1 Available
No anomalies in S1 voltage supply.
Source 2 Available
No anomalies in S2 voltage supply.
Load Shed 1
Used for shedding non-essential loads before
transferring to non-priority source. Signal is
activated before transferring to non-priority source
according to load shed delay and kept activated until
load is transferred back to priority source.
Continued on the next page
Содержание Zenith ZTG T Series
Страница 2: ...2 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 6: ...6 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 10: ...10 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 38: ...38 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 60: ...60 ZENITH ZTG D CT T SERIES 1600 3000 A 1 LCD ...
Страница 104: ...104 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 116: ...2 116 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 120: ...2 120 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Страница 123: ...123 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...