- 63 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
Control
Stations
Busfault
Automode
Force Local 2
Mode
Selection
enable
Starter
Function
(e.g. DOL)
Start
Stop
UMC
DI4
DI5
DI0
LCD
Panel
Digital
Inputs
Cyclic Bus
Telegram
Acyclic
Bus
Telegram
Bus
Super-
vision
...
Fieldbus
0
1
0
Activating Inching Mode
By default "pulses" are used to issue a start command. This means that a start input has to change its
logic level to issue a start command - i.e. it is edge triggered. After the start command was accepted from
the UMC the input signal can be set back to its initial value (e.g. zero).
For a start signal sent from the digital inputs (DI4/DI5) it is possible to change the behaviour from pulse
mode to inching mode. This means that the motor is only running while the start signal is present. If it is
not present anymore the motor stops automatically.
Relevant Parameters:
•
For each of the three modes Local Control 1 (Loc1), Local Control 2 (Loc2) and Auto (Auto) the following
parameters are available
- Start bus cyclic
- Stop bus cyclic
- Start LCD
- Stop LCD
- Start bus acyclic
- Stop bus acyclic
- Start DI
- Stop DI
•
Jog via DI (inching mode)
•
Invert start DI
•
Invert stop DI
Содержание UMC100-FBP
Страница 1: ...Technical Description Universal Motor Controller UMC100 FBP ...
Страница 8: ... 8 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 36: ... 36 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 90: ... 90 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 94: ... 94 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 108: ... 108 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 154: ... 154 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 156: ... 156 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 157: ......