Technical Description
FieldBusPlug / Issue: 03.2012
U
Dip
Restart
Level
Dip
Level
UMC Relay Out
Undervoltage situation
Dip Autorestart Window
DIP signal at
digital input
Dip
Auto-
restart
Delay
DIP Duration
Case b: The low voltage situation takes longer than the configured '
Dip Autorestart Window'
which
means the UMC switches off the relay output. But the low voltage situation is shorter than the configured
'
Dip Duration'
so the motor gets started automatically after an optional restart delay time (Parameter '
Dip
Autorestart Enable=On
). Otherwise it stays off.
Case c: The low voltage situation takes longer than the
'Dip Duration'
time. Therefore an error is gen-
erated as soon as the dip duration exceeds the configured dip duration time.
U
Dip
Restart
Level
Dip
Level
UMC Relay Out
Undervoltage situation
DIP signal at
digital input
Dip Duration
UMC Voltage
DIP Error
Содержание UMC100-FBP
Страница 1: ...Technical Description Universal Motor Controller UMC100 FBP ...
Страница 8: ... 8 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 36: ... 36 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 90: ... 90 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 94: ... 94 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 108: ... 108 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 154: ... 154 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 156: ... 156 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 157: ......