- 111 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
Indicator
Code
Source / Root Cause
Possible Cause / Suggested Ac-
tion
Earth fault (external or
internal sensor) above trip
threshold
12
Load side electrical
Connection between one or more
phases and ground
Check wiring / motor (isolation
problem)
Earthfault current above
warning threshold
13
Load side electrical
See above
UMC self-test error
14
Electronics
Hardware fault detected
Replace UMC
Actuator problem
15
Load side mechanics
Open/close time of actuator ex-
ceeded because of tight valve or
other mechanical reasons.
Check runtime parameter and limit
and torque switch wiring
IO module missing
16
Electronics, Wiring
Communication cable not con-
nected. Cable break or IO module
hardware error.
Custom application error
(e.g. download incom-
plete)
17
Configuration
An unrecoverable error was de-
tected while processing the custom
application (e.g. checksum error)
The version of application editor
and UMC are not compatible
IO module error
18
Electronics
A self-test error was detected in an
IO module.
Check the LEDs on the module
Replace the module
Aux1: Error or warning
triggered from auxiliary
function block input 0
19
User-defined
The digital input of an IO module
has created a trip/warning.
Reason depends on what you have
connected to the input.
Note: If the "AuxWarnFault" func-
tion block is used in a different way
than in the predefined applications
also other inputs than the DX1xx
can be the fault source.
Aux2: Error or warning
triggered from auxiliary
function block input 1
20
User-defined
Aux3: Error or warning
triggered from auxiliary
function block input 2
21
User-defined
Aux4: Error or warning
triggered from auxiliary
function block input 3
22
User-defined
Aux5: Error or warning
triggered from auxiliary
function block input 4
23
User-defined
Aux6: Error or warning
triggered from auxiliary
function block input 5
24
User-defined
Multifunction input 0
25
User-defined
A multifunction input of the UMC
has triggered a trip.
The reason depends on what you
have connected to the input.
Multifunction input 1
26
User-defined
Multifunction input 2
27
User-defined
Underload Power
34
Load side mechanics
The motor load is too low. Check
the load e.g. if a pump is running
dry or a conveyer load is broken.
Содержание UMC100-FBP
Страница 1: ...Technical Description Universal Motor Controller UMC100 FBP ...
Страница 8: ... 8 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 36: ... 36 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 90: ... 90 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 94: ... 94 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 108: ... 108 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 154: ... 154 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 156: ... 156 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 157: ......