- 123 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
Para-
meter
Number
Parameter
Description, Explanations
Options
Adjustable
via
Invert control (ctrl) Inputs
82
Inv DI start
input
If inverted (Yes) the DI is nor-
mally closed. If not inverted
(No) it is normally open.
No (0), Yes (1)
All
83
Inv DI stop
input
If inverted (Yes) the DI is nor-
mally closed. If not inverted
(No) it is normally open.
No (0), Yes (1)
Multifunction Inputs: The following parameters are all related to DI0-DI2 which are called
multifunction inputs as their function can be adjusted in a wide range.
(1.13)
117,
118,
119
Multif. 0,1,2
delay
Delay until the function of
DI0,1,2 is triggered
0...25,5 in steps of 0,1s
Unscaled: 0...255
Example: A value of 5 means
500ms
All
120,
121,
122
Multif. 0,1,2
auto reset
If DI0,1,2 is configured as
external fault an auto reset
can be enabled.
No (0),
Yes (1)
135/136
137/138
139/140
Multif. 0,1,2
fault text
Line 1, Line 2
If DI0,1,2 is configured as an
external fault a text message
can be defined which is
shown on the LCD panel.
Line one and line two with 8
characters each.
Default: „Fault DIx“ where
x=0,1,2
PBDTM,
LCD Panel
UMC100-
PAN
114,
115,
116
Multifunction
0,1,2
Function of DI0/1/2.
NC: Normally closed
NO: Normally open
1)
Motor running or stopped
2)
Always when the motor is
running
Off (0):
Stop NC (1),
Stop NO (2),
Ext. Flt NC always
1
(3),
Ext. Flt NO always
1
(4),
Ext. Flt NC Motor on (5),
Ext. Flt NO Motor on (6),
Prep. emergency start NC (7),
Prep. emergency start NO (8)
Test position NC (9),
Test position NO (10),
Force local NC (11)
Force local NO (12)
Fault reset NC (13),
Fault reset NO (14),
Voltage DIP NC (15),
Voltage DIP NO(16),
CEM11 always
2
(Warn) (17),
CEM11 after startup (Warn) (18),
CEM11 always
2
(Fault) (19),
CEM11 after startup (Fault) (20)
All
Extended
23
Checkback
time
The maximum delay between
the output relay was closed
until the checkback signal is
present (signal at DI0 present
or motor current > 20 %
depending on parameter
Checkback)
0.1, 0.2, 0.3, 0.4 ,0.5 ... 25.5
in steps of 0.1s
Unscaled: 0...255
Example: A value of 5 means
500ms
All exclu-
ding GSD-
PDQ22
Motor Management Parameters Continued
Содержание UMC100-FBP
Страница 1: ...Technical Description Universal Motor Controller UMC100 FBP ...
Страница 8: ... 8 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 36: ... 36 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 90: ... 90 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 94: ... 94 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 108: ... 108 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 154: ... 154 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 156: ... 156 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 157: ......