- 126 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
Para-
meter
Number
Parameter
Name
Description, Explanations
Options
Adjust-
able via
146
Thermal load
warning level
If the thermal model reaches
the warning level a warning is
generated.
20 ... 100
All ex-
cluding
GSD-
PDQ22
Locked Rotor
40
Locked rotor
trip level
Current in percentage that
should trigger a locked rotor
fault during motor start-up. A
value of 800% (160) switches
off the function.
100% ... 800% in steps of 5%
800% disables the function
Unscaled: 20 ... 160
Example: 100 means 500%
All
41
Locked rotor
trip delay
The time the motor current
must exceed the adjusted
threshold before a fault is trig-
gered.
0, 0.1, 0.2, 0.3, 0.4, 0.5 ... 25.5s
in steps of 0.1s
Unscaled: 0...255
Example: 5 means 500ms
All
Phases
42
Phase loss
protection
Trips the motor depending of
the trip class within 1.5 -12
seconds in case of a phase
loss. This parameter must be
set to On during regular opera-
tion.
Off (0), On (1)
Note: If the voltage module is present
this parameter activates both voltage and
current based phase loss detection.
All
43
Curr Imb Trip
Level
Phase imbalance (current) trip
threshold. Above this value a
trip is generated. A value of 100
disables the trip.
0...100%
100% disables the function
Default value: 50
All ex-
cluding
GSD-
PDQ22
44
Curr Imb
Warn Level
Phase imbalance (current)
warning threshold. Above this
value a warning is generated.
A value of 100 disables the
warning.
0...100%
100% disables the function
All ex-
cluding
GSD-
PDQ22
45
Phase
reversal
If enabled the three phases
must be fed through the UMC
CTs in the correct order (L1 left,
L2 middle, L3 right).
L1L2L3 (0),
L3L2L1 (1)
Note: If the voltage module is present
this parameter must not be changed.
All ex-
cluding
GSD-
PDQ22
46
Check phase
sequence
Enables supervision of phase
sequence (L1/L2/L3)
Disabled (0),
Trip (1),
Warning (2)
Note: If the voltage module is present
this parameter activates both voltage and
current based phase sequence protection.
All ex-
cluding
GSD-
PDQ22
Over - and Undercurrent
Protection Parameters Continued
Содержание UMC100-FBP
Страница 1: ...Technical Description Universal Motor Controller UMC100 FBP ...
Страница 8: ... 8 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 36: ... 36 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 90: ... 90 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 94: ... 94 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 108: ... 108 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 154: ... 154 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 156: ... 156 UMC100 FBP Universal Motor Controller UMC100 FBP Technical Description FieldBusPlug Issue 03 2012 ...
Страница 157: ......