9.6 Electrical Connection and Testing
Make all wiring work and make the appropriate tests according to chapter 7. Remove
the drying agent inside the cabinet of the motor-drive mechanism.
9.6.1 Motor Protection
The function of the protective motor switch is checked. For three-phase AC motors, one
of the phase fuses is removed and the function time of the protective motor switch is
checked by a RAISE or LOWER operation. The protective motor switch should release
within 60 seconds at a current setting equal to the rated current of the motor at the
actual voltage.
CAUTION
If the protective motor switch has not released within 60 seconds, disconnect the
power and check the settings with the rating plate of the motor. Adjust if necessary
and check again when the motor has cooled down.
WARNING
The motor power voltage is dangerous.
Protective motor switches for DC motors and for single-phase AC motors are not
tested.
9.6.2 Disc Brake
For BUE:
Run the motor-drive mechanism and check again that the red mark on the brake disc
stops within the tolerance of ±25 degrees from exact position, see Fig. 39. For
adjustment, see
1ZSE 5492-126, Maintenance Guide for UCC and UCD.
9.6.3 Counter
Check that the counter is functioning at RAISE and LOWER operations.
9 Commissioning