Waste and cleaning up: Should be absorbed by an absorber. Treat it as hazardous
to the environment.
Upon fire: The fire should be extinguished by using powder, foam or carbon acid.
WARNING
Be aware of the risk for slipperiness caused by oil spillage for instance when
working on the transformer cover.
WARNING
The motor-drive mechanism must not be installed in any explosive atmosphere.
The electrical equipment creates sparks which can cause an
explosion.
WARNING
Before any work is carried out on the on-load tap-changer:
Make sure that the transformer is disconnected and that earthing is properly
carried out. Obtain a signed certificate from the engineer in charge.
WARNING
Before carrying out work on the on-load tap-changer, put the LOCAL/REMOTE
switch in the motor-drive mechanism to position 0. It is also recommended to shut
the door of the motor-drive mechanism and pad lock it when work is carried out
on the on-load tap-changer. The key should be kept by the operator. This is done
to avoid unexpected start of the motor-drive mechanism.
WARNING
Before starting any work inside the motor-drive mechanism, the auxiliary power
must be switched off.
N.B. The motor, contactors and heating element may be energized from separate
sources.
During Drying of the Transformer
CAUTION
The diverter switch should not be installed during drying, since the process removes
grease needed for operation.
CAUTION
During drying with hot air and vacuum, the maximum permitted pressure difference
for the diverter switch housing is 100 kPa at the maximum permitted temperature of
135
o
C (275
o
F).