![ABB UCC Series Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/abb/ucc-series/ucc-series_installation-and-commissioning-manual_3710020.webp)
20
3 Installation in the Transformer
4. Lift the diverter switch housing in the lifting eyes as shown in Fig. 3 and lower it
carefully through the opening in the transformer top cover, see Fig. 4. Place the
diverter switch housing correctly in position for mounting the outer shaft system
(see transformer drawing). The studs on the flange on the transformer cover shall
fit into the holes in the flange of the diverter switch housing.
Mount thirty washers and M16 nuts, see Fig. 5. Tighten the nuts.
5. If the impulse withstand voltage exceeds 380 kV, mount first the upper of the two
dismantled shielding rings on the diverter switch housing and then the lower, see
Fig. 7.
6. Put the tap selector in position for joining to the diverter switch housing. Lift in
the lifting eyes as shown in Fig. 3.
7a. In case the on-load tap-changer is equipped with a tie-in resistor for mounting
under the tap selector, the tie-in resistor should be mounted after joining the tap
selector to the diverter switch housing. After mounting the tie-in resistor, the on-
load tap-changer must not be put down standing on the tie-in resistor. It must be
hanging, for instance in a traverse.
WARNING
To put down the on-load tap-changer to stand on the floor with the tie-in resistor
mounted means a great risk for tilting the on-load tap-changer with risk for
injuries to people and damage of the equipment.
7b. In case the on-load tap-changer is equipped with a tie-in resistor switch, the
switch is mounted under the tap selector at delivery. A special support in the box
makes it standing on the tap selector bottom. If this special support is taken out of
the box, the tap selector can be standing on this during joining to the diverter
switch housing. After joining, the complete on-load tap-changer is lifted and the
special support is removed. The complete on-load tap-changer must not be put on
the special support. It must be hanging, for instance in a traverse.
WARNING
To put down the on-load tap-changer to stand on the floor with the tie-in resistor
switch mounted means a great risk for tilting the on-load tap-changer with risk for
injuries to people and damage of the equipment.
8. Remove the transport locking and the lifting eyes with fasteners from the top
section of the tap selector, see Fig. 6.
CAUTION
Do not operate the tap selector until it is connected to the diverter switch housing.