19
When the first three ways of operation are used
the OPEN and CLOSE outputs deliver pulses.
Before an output can be activated the operation
must be enabled by the interlocking logic.
The open and close pulse lengths of the outputs
are determined by SPA bus variables V5 and V6.
The pulse length has to be determined for the
input channels to which the objects to be con-
trolled are connected.
The pulse lenght can be set within the range
0.1…100 s with a time resolution of 0.1 s.
Example 10:
The pulse lenghts can be set in the operation
mode. The following SPA bus commands are
used to program the open and close pulse lengths.
The object is configured to input channel 2.
>99W2V5:0.5:XX
; Set the open pulse length at 0.5 seconds
>99W2V6:0.2:XX
; Set the close pulse length at 0.2 seconds
>99WV151:1:XX
; Store the programmed parameters
The open and close commands are given via
serial communication to the input channel on
which the object to be controlled is located. The
outputs OPEN1…6 and CLOSE1…6 can be
controlled via serial communication according
to two principles:
- Direct control: An output command is given
by using parameter O1. When this parameter
has been given the value 0 (open) or 1 (close)
the corresponding output pulse is given pro-
vided the operation is enabled by the inter-
locking program.
- Secured control: Initially the output is set into
a state of alert by means of parameter V1 for
opening and parameter V2 for closing. After
that the output command is executed by means
of parameter V3, if enabled by the interlock-
ing program. The state of alert is automati-
cally cancelled when the execute command
has been given. The state of alert can also be
cancelled by parameter V4.
The control module SPTO 6D3 has 14 outputs:
two signal outputs (SIGNAL5 and 6) and 12
control outputs (OPEN1…6 and CLOSE1…6).
For the purpose of setting the outputs are coded
as follows:
Output
Output code for Output code for
configuration
Direct Output
and interlocking Control
OPEN1
20
220
CLOSE1
21
221
OPEN2
22
222
CLOSE2
23
223
OPEN3
24
224
CLOSE3
25
225
OPEN4
26
226
CLOSE4
27
227
OPEN5
28
228
CLOSE5
29
229
OPEN6
30
230
CLOSE6
31
231
SIGNAL5
40
40
SIGNAL6
41
41
The outputs OPEN1 and CLOSE1, OPEN2
and CLOSE2 etc. always form pairs. The OPEN
output is used to open an object and the CLOSE
output is used to close the same object.
The OPEN and CLOSE outputs can be con-
trolled in four ways:
- Locally by means of the OPEN and CLOSE
push buttons on the front panel of the control
module
- Remotely with commands via the SPA bus
- Remotely via the binary inputs 8…17, see
chapter "Input channels 8…17"
- By the Direct Output Control logic, see chap-
ter "Direct Output Control"
In addition, the OPEN and CLOSE outputs are
controlled by the auto-reclose unit, if the AR
functions are in use.
For the selection of the objects to be controlled
via the OPEN and CLOSE outputs, see chapter
"Configuration".