6
The setting values are shown by the three
rightmost digits of the display. When lit, the
indicator below a setting knob shows that the
concerned setting value is being displayed.
I>/I
n
Set start current of stage I> as a multiple of the rated current I
n
of the energizing input
used. Setting range 0.5...2.5 x I
n
.
t> [s]
The set start time of stage I>, expressed in seconds, when the definite time characteristic
k
is used (SG1/3 = 0). The setting range is determined by the position of switches SG1/1
and SG1/2. Selectable setting ranges 0.05...1.00 s, 0.5...10.0 s and 5...100 s.
At inverse definite minimum time characteristic (SG1/3 = 1) the setting range of time
multiplier k is 0.05...1.00.
I>>/I
n
Set starting current of stage I>> as a multiple of the rated current I
n
of the energizing input
used. Setting range 2.5...20.0 x I
n
, when SG1/6 = 0, and 0.5...4.0 x I
n
, when SG1/6 = 1.
Additionally, the setting infinite (displayed as - - -) can be selected, rendering the high-
set stage I>> inoperative.
t>> [s] The set operation time of stage I>>, expressed in seconds. The setting ranges, 0.04...1.00 s,
0.4...10.0 s and 4...100 s, are determined by the position of switches SG1/7 and SG1/8, see
below.
Settings
Further, the checksum of the selector switch-
group SG1 is indicated on the display when the
indicator under the switchgroup is glowing. In
this way a checked can be carried out to prove
that the switches have been set and that the
switches themselves work properly. An example
of calculating the checksum is given in the
description "General characteristics of C-type
relay modules".