20
and some other data. Further, part of the data
can be altered by commands given over the SPA
bus. Any information is located on channel 0,
which needs not to be written in the data com-
munication instructions.
Remote transfer
data
Apart from the event codes the control data
communicator is able to read, over the SPA bus,
all input data (I data) of the relay module, set
values (S values), output status data (O data)
information recorded in the memory (V data),
Data
Code
Data
Values
direct.
Current on phase L1 as a multiple
I1
R
0...63 x I
n
of the rated current
Current on phase L2 as a multiple
I2
R
0...63 x I
n
of the rated current
Current on phase L3 as a multiple
I3
R
0...63 x I
n
of the rated current
Blocking of tripping of stage I>
I4
R
0 = no blocking
1 = tripping of stage I> blocked
Blocking of tripping of stage I>>
I5
R
0 = no blocking
1 = tripping of stage I>> blocked
Starting of stage I>
O1
R
0 = stage I> has not started
1 = stage I> started
Tripping of stage I>
O2
R
0 = stage I> not tripped
1 = stage I> tripped
Starting of stage I>>
O3
R
0 = stage I>> not started
1 = stage I>> started
Tripping of stage I>>
O4
R
0 = stage I>> not tripped
1 = stage I>> tripped
Alerted start value for stage I>
S1
R
0.5...2.5 x I
n
Alerted operation time for stage I>
S2
R
0.05...100 s
or time multiplier k
0.05...1.00
Alerted start value for stage I>>
S3
R
0.5...20 x I
n
999 =
∞
, infinite
Alerted operation time for stage I>>
S4
R
0.04...100 s
Alerted checksum of switchgroup SG1
S5
R
0...255
Start value of stage I>, set with
S11
R
0.5...2.5 x I
n
the setting knob
Operation time or time multiplier of
S12
R
0.05...100 s
stage I>, set with the setting knob
0.05...1.00
Start value of stage I>>, set with
S13
R
0.5...20 x I
n
the setting knob
999 =
∞
, infinite
Operation time of stage I>>, set
S14
R
0.04...100 s
with the setting knob
Checksum of switchgroup SG1,
S15
R
0...255
set with the switches
Remote setting percentage of the
S21
R, W
0...999%
start value of stage I>
Remote setting percentage of the
S22
R, W
0...999%
operation time or time multiplier
of stage I>
Remote setting percentage of the
S23
R, W
0...999%
start value of stage I>>
Remote setting percentage of the
S24
R, W
0...999%
operation time of stage I>>
Remotely set checksum for the
S25
R, W
0...255
switchgroup SG1