41
Data
Channel Code
Data
Values
direction
No. of AR cycles 2 initiated by AR1 0
V25
RW
0…999
No. of AR cycles 2 initiated by AR2 0
V26
RW
0…999
No. of AR cycles 2 initiated by AR3 0
V27
RW
0…999
Total number of AR cycles 3
0
V28
R
0…999
No. of AR cycles 3 initiated by AR1 0
V29
RW
0…999
No. of AR cycles 3 initiated by AR2 0
V30
RW
0…999
No. of AR cycles 3 initiated by AR3 0
V31
RW
0…999
Total number of AR cycles 4
0
V32
R
0…999
No. of AR cycles 4 initiated by AR1 0
V33
RW
0…999
No. of AR cycles 4 initiated by AR2 0
V34
RW
0…999
No. of AR cycles 4 initiated by AR3 0
V35
RW
0…999
Total number of AR cycles 5
0
V36
R
0…999
No. of AR cycles 5 initiated by AR1 0
V37
RW
0…999
No. of AR cycles 5 initiated by AR2 0
V38
RW
0…999
No. of AR cycles 5 initiated by AR3 0
V39
RW
0…999
Store data into EEPROM
0
V151
W
1=storing, takes about 5 s
Load default values after EEPROM
0
V152
RW(e) 0=enable loading of default values
failure
1=inhibit loading of default values
Event mask
0
V155
RW(e) 0…1023
Event mask
0
V156
RW(e) 0…1023
Event mask
0
V157
RW(e) 0…1023
Event mask
0
V158
RW(e) 0…2047
Event mask
1…7
V155
RW(e) 0…2047
Event mask
8…17
V155
RW(e) 0…15
Activation of self-supervision
0
V165
W
0=reset
output
1=activate
Internal fault code
0
V169
R
Fault code
Data communication address
0
V200
RW(e) 1…254
Data transfer rate
0
V201
RW(e) 4800, 9600
Program version symbol
0
V205
R
E.g. 055 M
Type designation of the module
0
F
R
SPTO 6D3
Reading of event register
0
L
R
Time, channel number and
event code
Re-reading of event register
0
B
R
Time, channel number and
event code
Reading of module status
0
C
R
0=normal state
information
1=module been subject to
automatic reset
2=overflow of event register
3=events 1 and 2 together
Resetting of module status
0
C
W
0=resetting
information
Time reading and setting
0
T
RW
0.000…59.999 s
R
= Data which can be read from the module
W = Data which can be written to the module
(e) = Data which has to be stored in EEPROM (V151) after it has been changed
The event register can be read by the L com-
mand only once. Should a fault occur e.g. in the
data transfer, it is possible, by using the B
command, to re-read the contents of the event
register. When required, the B command can be
repeated.
The data transfer codes L, B, C and T have been
reserved for event data transfer between the
control module and the station level data com-
municator.