6
lit, the setting value curently being shown on
the display.
Settings
The setting values are shown by the three
rightmost green digits of the display. The LED
indicator below the setting knob shows, when
I
ϕ
>/I
n
Start current of stage I
ϕ
>, expressed as a percentage of the rated current of the
energized relay input. Setting range 1...10% x I
n
.
t> [s]
Operate time of stage I
ϕ
>, expressed in seconds. The setting range is 0.1...1.0 seconds
when SG1/5 = 0, and 1.0...10.0 seconds when SG1/5 = 1.
I
ϕ
>>/I
n
Start current of stage I
ϕ
>>, expressed as a percentage of the rated current of the
energized relay input. The setting range is 5...40% x I
n
when SG1/6 = 0, and 1...8%
x I
n
when SG1/6 = 1. Additionally, the setting
∞
, infinite (displayed as- - -) can be
selected, which means that stage I
ϕ
>> has been set out of function. If the high-set stage
I
ϕ
>> operates in the reverse direction (SG1/1 = 1), the setting value is negative and
the leftmost digit on the display shows a red minus sign.
t>> [s]
Operate time of stage I
ϕ
>>, expressed in seconds. Setting range 0.1...1.0 seconds.
Further, the checksum of the selector switch-
group SG1 is presented on the display when the
LED indicator under the switchgroup is lit. In
this way the proper operation of the selector
switches can be verified. An example illustrating
the manual procedure for calculating the
checksum is given in the manual "General char-
acteristics of C type relay modules".