1MRS755014
SPA-ZC 302
65
Profibus-DPV1/SPA Gateway
Installation and Commissioning Manual
1)
These error codes are followed by more data in the diagnostics fields, such as SPA Channel, SPA Type
and SPA Dno (Parameter No) for easier location of the trouble spot. For all other error situations,
these fields will be set to zero.
2. Event Buffer section
Slv
Slave address from which the event has been read
Sec
Seconds when the event occurred
Msec
Milliseconds when the event occurred
Ch
Communication channel on which the event occurred
Type
Type of event that occurred
Nr
Event number
Val
Value of the event
3. Module section
SPA Gateway Time
Set time in the gateway
Module Status Word
Status of the gateway. This word is sent to the master as
the first word in each input data block. The definition of
the bits is described in Section 6.1. Module status word.
4. SPA messages statistics section
Transmitted
Number of SPA messages transmitted
Correct
Number of correctly formed SPA messages
NACK’s received
Number of NACK (Negative Acknowledgement)
responses received from the SPA slave
Table 8.4.1-1
Configuration error types
Error Type
Description
Configuration OK
No problem detected in the configuration file.
Configuration Empty
The gateway was not able to locate any configuration.
CRC Failure
The gateway was not able to verify the CRC of the
configuration file.
Unsupported Baudrate
The gateway was not able to use the configured baudrate.
Unsupported Reply Timeout
The gateway was not able to use the configured Reply
Timeout.
Unsupported Idle Time
The gateway is not able to use the configured Idle Time.
Unsupported Retry Count
The gateway is not able to use the configured Retry Count.
Unsupported PDP Default
Address
The gateway is not able to use the configured Profibus
Default Address.
Unsupported Decimal Place
The gateway is not able to use the configured Decimal
Place.
Analog Input Error
1)
Error in one of the Analog Input settings.
Digital Input Error
1)
Error in one of the Digital Input settings.
Analog Output Error
1)
Error in one of the Analog Output settings.
Digital Output Error
1)
Error in one of the Digital Output settings.
Indirect SPA Error
1)
Error in one of the Indirect SPA settings.