22
1MRS755014
Profibus-DPV1/SPA Gateway
Installation and Commissioning
SPA-ZC 302
3.3.3.4.
RS-485/SPA bus cable
Fig. 3.3.3.4.-1 Interface cable coupling when using RS-485 (Order
number:1MRS120541)
3.3.3.5.
RS-485/SPA bus cable
A050352
Fig. 3.3.3.5.-1 Interface cable coupling when using RS-485 with, for example,
REX 521, RE_610, SACO annunciator unit
Table 3.3.3.4-1 Pin numbers of the SPA bus/RS-485 connection
Pin
Usage
1
DATA A, data signal pair, signal A (+)
2
DATA B, data signal pair, signal B (-)
3
RTS A, request to send signal pair, signal A (+)
4
RTS B, request to send signal pair, signal B (-)
7
GND, signal ground
9
+8V, optional power supply from the SPA-ZC 302
SPA-ZC 302 SPA device, RS-485
9-pin female D-connector 9-pin male D-connector
1
2
3
4
7
9
1
2
3
4
7
9
cable485_a
Table 3.3.3.5-1 Pin numbers of the SPA bus/RS-485 connection
Pin
Usage
1
DATA A, data signal pair, signal A (+)
2
DATA B, data signal pair, signal B (-)
SPA-ZC 302
SPA device, RS-485
1
2
9-pin female D-connector
Terminal Block